CA2KN22M7 | TeSys K control relay – 2 NO + 2 NC – <= 690 V - 220...230 V AC coil - Schneider Electric
₹3,090.00 Original price was: ₹3,090.00.₹1,390.50Current price is: ₹1,390.50. Excl. GST
In stock
In stock
Order protection
Buy with complete confidence.
We back each order with genuine supply, on-time dispatch and GST or commercial invoicing as required.
Sourced through authorised channels, the Schneider Electric CA2KN22M7 relay from the TeSys range delivers dependable performance for motor control and switching. Key ratings include <= 690 V <= 400 Hz, IP2X. myelectric.in stocks the CA2KN22M7 | TeSys K control relay - 2 NO + 2 NC - <= 690 V - 220...230 V AC coil for contractors, panel builders, and project buyers — buy online with GST invoice, or request a bulk quote for domestic supply and export to UAE, Singapore, UK, USA, Sri Lanka and more.
📋 Technical Specifications
| Product | |
| Brand | Schneider Electric |
| Part Number / SKU | CA2KN22M7 |
| Category | Relay |
| Main | |
| Range | TeSys |
| Product name | TeSys CAK |
| Product or component type | Control relay |
| Device short name | CA2K |
| Contactor application | Control circuit |
| Utilisation category | AC-15 DC-13 |
| Pole contact composition | 2 NO + 2 NC |
| [Ue] rated operational voltage | <= 690 V <= 400 Hz |
| Control circuit type | AC at 50/60 Hz |
| [Uc] control circuit voltage | 220…230 V AC 50/60 Hz |
| Complementary | |
| [Ith] conventional free air thermal current | 10 A (at 50 °C) |
| Irms rated making capacity | 110 A conforming to IEC 60947 |
| Associated fuse rating | 10 A gG conforming to IEC 60947 10 A gG conforming to VDE 0660 |
| [Ui] rated insulation voltage | 690 V conforming to IEC 60947 750 V conforming to VDE 0110 group C 690 V conforming to BS 5424 600 V conforming to CSA C22.2 No 14 |
| Mounting support | Rail Plate |
| Connections – terminals | Screw clamp terminals 1 cable(s) 1.5…4 mm²solid Screw clamp terminals 2 cable(s) 1.5…4 mm²solid Screw clamp terminals 1 cable(s) 0.75…4 mm²flexible with cable end Screw clamp terminals 2 cable(s) 0.75…4 mm²flexible without cable end Screw clamp terminals 1 cable(s) 0.34…1.5 mm²flexible with cable end Screw clamp terminals 2 cable(s) 0.34…1.5 mm²flexible without cable end |
| Tightening torque | 1.3 N.m – on screw clamp terminals – with screwdriver flat Ø 6 mm 1.3 N.m – on screw clamp terminals – with screwdriver Philips No 26 mm 1.3 N.m – on screw clamp terminals – with screwdriver pozidriv No 2 |
| Control circuit voltage limits | Drop-out: 0.2…0.75 Uc (at <50 °C) Operational: 0.8…1.15 Uc (at <50 °C) |
| Operating time | 10…20 ms coil de-energisation and NO opening 10…20 ms coil energisation and NO closing 15…25 ms coil de-energisation and NC closing 5…15 ms coil energisation and NC opening |
| Mechanical durability | 10 Mcycles |
| Maximum operating rate | 10000 cyc/h |
| Immunity to microbreaks | 2 ms |
| Inrush power in VA | 30 VA (at 20 °C) |
| Hold-in power consumption in VA | 4.5 VA (at 20 °C) |
| Heat dissipation | 1.3 W |
| Minimum switching voltage | 17 V |
| Minimum switching current | 5 mA |
| Non overlap distance | 0.5 mm |
| Insulation resistance | > 10 MOhm |
| Height | 58 mm |
| Width | 45 mm |
| Depth | 57 mm |
| Product weight | 0.18 kg |
| Environment | |
| Standards | EN/IEC 60947-5-1 GB/T 14048.5 UL 60947-5-1 CSA C22.2 No 60947-5-1 JIS C8201-5-1 |
| Product certifications | CB Scheme CCC UL CSA EAC CE UKCA |
| IP degree of protection | IP2X |
| Protective treatment | TC conforming to IEC 60068 |
| Ambient air temperature for operation | -25…50 °C |
| Ambient air temperature for storage | -50…80 °C |
| Operating altitude | 2000 m without derating |
| Flame retardance | V1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102 |
| Mechanical robustness | Vibrations contactor open: 2 Gn, 5…300 Hz conforming to IEC 60068-2-6 Vibrations contactor closed: 4 Gn, 5…300 Hz conforming to IEC 60068-2-6 Shocks contactor open: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed: 15 Gn for 11 ms conforming to IEC 60068-2-27 |
| Packing Units | |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 6.500 cm |
| Package 1 Width | 6.100 cm |
| Package 1 Length | 4.800 cm |
| Package 1 Weight | 178.000 g |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 50 |
| Package 2 Height | 15.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 9.230 kg |
| Contractual warranty | |
| Warranty (in months) | 18 |
⚡ Key Features
- 2 NO (normally-open) contacts for load switching and sequencing; 2 NC (normally-closed) contacts for interlocking, fail-safe, and alarm circuits — all contacts independently switchable up to the contact voltage rating.
- 220–230V AC coil — energises from PLC digital output (transistor or relay type), timer contact, or pushbutton; no separate relay driver card required.
- Contact voltage rating 690V AC — switches 230V AC loads (solenoid valves, motor starters, indicator lamps) and DC loads (PLC inputs, LED panels) within the same contact rating.
- TeSys K control relay — identical DIN rail footprint to TeSys D contactors; accepts LA1KN auxiliary contact blocks for additional NO/NC outputs; mountable on 35mm or 20mm DIN rail.
- Manufactured to IEC 60947-5-1 — complies with the applicable Indian BIS and IEC international standards for this product category.
- BIS certified, CE marked, RoHS compliant — meets Indian regulatory requirements for use in government, commercial, and industrial electrical installations.
- Genuine authorised Schneider Electric product — sourced directly from the official distribution network with full manufacturer traceability and warranty.
- GST invoice provided for India orders — valid for corporate procurement, government project orders, and public tender supply via myelectric.in.
- Worldwide export available — UAE, Singapore, UK, USA, Sri Lanka & more. Contact +91 94814 00316 for bulk pricing and international shipping.
🔗 Compatible Products & Accessories
The following genuine accessories and compatible devices are designed to work with this product. Contact myelectric.in for pricing and availability:
❓ Frequently Asked Questions
Q: The CA2KN22M7 has a coil voltage of 220–230V AC — what control supply is needed?
A: This Schneider Electric device requires a 220–230V AC control supply connected to the coil terminals (A1 and A2). For AC coils, ensure the control circuit voltage is stable — voltage drops below 85% of rated coil voltage can cause chatter and coil overheating. Always fit a surge suppressor across the coil when switching with a PLC or solid-state relay.
Q: What circuit can the 2 NO + 2 NC contacts of the CA2KN22M7 switch at 690V AC?
A: The 2 NO + 2 NC contacts on the CA2KN22M7 are rated for switching at up to 690V AC. These auxiliary contacts are typically used for: (1) indication lamps and buzzers, (2) PLC input feedback to confirm device state, (3) interlocking with other contactors or relays in control circuits. Check the current rating of the auxiliary contact (typically 10A at 250V AC) — do not use for power load switching.
Q: How do I test the CA2KN22M7 relay in the field without a signal source?
A: Most Schneider Electric relays can be manually forced using the test button (if fitted) — this mechanically closes the relay contacts without energising the coil, allowing functional testing of the controlled circuit. For coil testing, use a multimeter to measure coil resistance (typically 500–2000Ω for AC coils at rated voltage) and compare with datasheet values.
Q: Can the CA2KN22M7 relay be mounted on a DIN rail socket for easy replacement?
A: This Schneider Electric relay typically requires direct panel or DIN rail wiring. For applications requiring frequent relay replacement, consider the plug-in relay variant of this series with a matching socket base.