LC1D65ABBE TeSys D contactor 3P 65A AC-3 up to 440V coil 24V DC EverLink Schneider Electric lc1d65abbe image 1 1500x1500
LC1D65ABBE | TeSys D contactor 3P 65A AC-3 up to 440V coil 24V DC EverLink - Schneider Electric Original price was: ₹36,970.00.Current price is: ₹16,636.50. Excl. GST
Back to products
LC1D65ABNE TeSys D contactor 3P 65A AC-3 up to 440V coil 24-60V AC DC coil EverLink Schneider Electric lc1d65abne image 1 150
LC1D65ABNE | TeSys D contactor 3P 65A AC-3 up to 440V coil 24-60V AC/DC coil EverLink - Schneider Electric Original price was: ₹36,970.00.Current price is: ₹16,636.50. Excl. GST

LC1D65ABD | TeSys D contactor – 3P(3 NO) – AC-3 – <= 440 V 65 A - 24 V DC standard coil - Schneider Electric

SKU: LC1D65ABD

Original price was: ₹39,185.00.Current price is: ₹17,633.25. Excl. GST

In stock

In stock

My Electric Support Online · Mon–Sat 9am–6pm IST
Product enquiry
Order on WhatsApp SKU: LC1D65ABD

Same-day dispatch · GST invoice available

16 People watching this product now!

Order protection

Buy with complete confidence.

We back each order with genuine supply, on-time dispatch and GST or commercial invoicing as required.

Buyer protection on every order
Global DeliveryShipped pan-India and to export markets.
On-Time DeliveryPacked and dispatched on schedule.
100% OriginalFrom brand-authorised channels only.
GST InvoiceCompliant, ITC-ready tax invoice.
Secure PaymentEncrypted, trusted payment gateways.
Also included Dedicated account manager Technical support Bulk & business pricing 3-day replacement

Looking for the LC1D65ABD | TeSys D contactor – 3P(3 NO) – AC-3 – <= 440 V 65 A - 24 V DC standard coil? This genuine Schneider Electric contactor from the TeSys range is built for motor control and switching, combining proven reliability with full compliance to applicable IEC/IS standards. Key ratings include 80 A, Power circuit: <= 690 V AC 25...400 Hz, 3P. Order part number LC1D65ABD from myelectric.in — a trusted Schneider Electric supplier offering competitive pricing, GST billing, and shipping across India and overseas.

📋 Technical Specifications

Product
BrandSchneider Electric
Part Number / SKULC1D65ABD
CategoryContactor
Main
RangeTeSys
TeSys Deca
Range of productTeSys Deca
Product or component typeContactor
Device short nameLC1D
Contactor applicationMotor control
Resistive load
Utilisation categoryAC-3
AC-3e
AC-1
AC-4
Poles description3P
[Ue] rated operational voltagePower circuit: <= 690 V AC 25…400 Hz
Power circuit: <= 300 V DC
[Ie] rated operational current80 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
65 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
65 A (at <60 °C) at <= 440 V AC AC-3e for power circuit
[Uc] control circuit voltage24 V DC
Complementary
Motor power kW18.5 kW at 220/230 V AC 50/60 Hz (AC-3)
30 kW at 380/400 V AC 50/60 Hz (AC-3)
37 kW at 500 V AC 50/60 Hz (AC-3)
37 kW at 660/690 V AC 50/60 Hz (AC-3)
18.5 kW at 220/230 V AC 50/60 Hz (AC-3e)
30 kW at 380/400 V AC 50/60 Hz (AC-3e)
37 kW at 500 V AC 50/60 Hz (AC-3e)
37 kW at 660/690 V AC 50/60 Hz (AC-3e)
11 kW at 400 V AC 50/60 Hz (AC-4)
Motor power hp40 hp at 460/480 V AC 50/60 Hz for 3 phases motors
5 hp at 115 V AC 50/60 Hz for 1 phase motors
10 hp at 230/240 V AC 50/60 Hz for 1 phase motors
20 hp at 200/208 V AC 50/60 Hz for 3 phases motors
20 hp at 230/240 V AC 50/60 Hz for 3 phases motors
50 hp at 575/600 V AC 50/60 Hz for 3 phases motors
Compatibility codeLC1D
Pole contact composition3 NO
Protective coverWith
[Ith] conventional free air thermal current10 A (at 60 °C) for signalling circuit
80 A (at 60 °C) for power circuit
Irms rated making capacity140 A AC for signalling circuit conforming to IEC 60947-5-1
250 A DC for signalling circuit conforming to IEC 60947-5-1
1000 A at 440 V for power circuit conforming to IEC 60947
Rated breaking capacity1000 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current640 A 40 °C – 10 s for power circuit
900 A 40 °C – 1 s for power circuit
110 A 40 °C – 10 min for power circuit
260 A 40 °C – 1 min for power circuit
100 A – 1 s for signalling circuit
120 A – 500 ms for signalling circuit
140 A – 100 ms for signalling circuit
Associated fuse rating10 A gG for signalling circuit conforming to IEC 60947-5-1
125 A gG at <= 690 V coordination type 1 for power circuit
125 A gG at <= 690 V coordination type 2 for power circuit
Average impedance1.5 mOhm – Ith 80 A 50 Hz for power circuit
Power dissipation per pole9.6 W AC-1
6.3 W AC-3
6.3 W AC-3e
[Ui] rated insulation voltagePower circuit: 600 V CSA certified
Power circuit: 600 V UL certified
Signalling circuit: 690 V conforming to IEC 60947-1
Signalling circuit: 600 V CSA certified
Signalling circuit: 600 V UL certified
Power circuit: 690 V conforming to IEC 60947-4-1
Overvoltage categoryIII
Pollution degree3
[Uimp] rated impulse withstand voltage6 kV conforming to IEC 60947
Safety reliability levelB10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Mechanical durability10 Mcycles
Electrical durability0.5 Mcycles 80 A AC-1 at Ue <= 440 V
1.45 Mcycles 65 A AC-3 at Ue <= 440 V
1.45 Mcycles 65 A AC-3e at Ue <= 440 V
Control circuit typeDC standard
Coil technologyBuilt-in bidirectional peak limiting diode suppressor
Control circuit voltage limits0.1…0.3 Uc (-40…70 °C):drop-out DC
0.75…1.25 Uc (-40…60 °C):operational DC
1…1.25 Uc (60…70 °C):operational DC
Inrush power in W19 W (at 20 °C)
Hold-in power consumption in W7.4 W at 20 °C
Operating time50 ±15 % ms closing
16…24 ms opening
Time constant34 ms
Maximum operating rate3600 cyc/h at 60 °C
Connections – terminalsControl circuit: screw clamp terminals 2 1…2.5 mm² – cable stiffness: flexible with cable end
Control circuit: screw clamp terminals 1 1…4 mm² – cable stiffness: flexible without cable end
Control circuit: screw clamp terminals 2 1…4 mm² – cable stiffness: flexible without cable end
Control circuit: screw clamp terminals 1 1…4 mm² – cable stiffness: flexible with cable end
Control circuit: screw clamp terminals 1 1…4 mm² – cable stiffness: solid without cable end
Control circuit: screw clamp terminals 2 1…4 mm² – cable stiffness: solid without cable end
Power circuit: screw clamp terminals 1 1…35 mm² – cable stiffness: flexible without cable end
Power circuit: screw clamp terminals 2 1…25 mm² – cable stiffness: flexible without cable end
Power circuit: screw clamp terminals 1 1…35 mm² – cable stiffness: flexible with cable end
Power circuit: screw clamp terminals 2 1…25 mm² – cable stiffness: flexible with cable end
Power circuit: screw clamp terminals 1 1…35 mm² – cable stiffness: solid without cable end
Power circuit: screw clamp terminals 2 1…25 mm² – cable stiffness: solid without cable end
Tightening torqueControl circuit: 1.7 N.m – on EverLink BTR screw connectors – with screwdriver flat Ø 6 mm
Control circuit: 1.7 N.m – on EverLink BTR screw connectors – with screwdriver Philips No 2
Power circuit: 8 N.m – on EverLink BTR screw connectors – cable 25…35 mm² hexagonal screw head 4 mm
Power circuit: 5 N.m – on EverLink BTR screw connectors – cable 1…25 mm² hexagonal screw head 4 mm
Control circuit: 1.7 N.m – on EverLink BTR screw connectors – with screwdriver pozidriv No 2
Power circuit: 2.5 N.m – on EverLink BTR screw connectors – with screwdriver pozidriv No 2
Auxiliary contact composition1 NO + 1 NC
Auxiliary contacts typetype mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
type mirror contact 1 NC conforming to IEC 60947-4-1
Signalling circuit frequency25…400 Hz
Minimum switching voltage17 V for signalling circuit
Minimum switching current5 mA for signalling circuit
Insulation resistance> 10 MOhm for signalling circuit
Non-overlap time1.5 ms on de-energisation between NC and NO contact
1.5 ms on energisation between NC and NO contact
Mounting supportPlate
Rail
Environment
StandardsEN 60947-4-1
EN 60947-5-1
IEC 60947-4-1
IEC 60947-5-1
CSA C22.2 No 14
UL 60947-4-1
IEC 60335-2-40:Annex JJ
UL 60335-2-40:Annex JJ
IEC 60335-1:Clause 30.2
Product certificationsCCC
UL
CB Scheme
CSA
CE
UKCA
Marine
EAC
IP degree of protectionIP20 front face conforming to IEC 60529
Protective treatmentTH conforming to IEC 60068-2-30
Climatic withstandconforming to IACS E10 exposure to damp heat
conforming to IEC 60947-1 Annex Q category D exposure to damp heat
Permissible ambient air temperature around the device-40…60 °C
60…70 °C with derating
Operating altitude0…3000 m
Fire resistance850 °C conforming to IEC 60695-2-1
Mechanical robustnessVibrations contactor open (2 Gn, 5…300 Hz)
Vibrations contactor closed (4 Gn, 5…300 Hz)
Shocks contactor closed (15 Gn for 11 ms)
Shocks contactor open (10 Gn for 11 ms)
Height122 mm
Width55 mm
Depth120 mm
Product weight0.935 kg
Packing Units
Unit Type of Package 1PCE
Number of Units in Package 11
Package 1 Height6.200 cm
Package 1 Width13.500 cm
Package 1 Length15.200 cm
Package 1 Weight984.000 g
Unit Type of Package 2S02
Number of Units in Package 210
Package 2 Height15.000 cm
Package 2 Width30.000 cm
Package 2 Length40.000 cm
Package 2 Weight10.390 kg
Unit Type of Package 3P06
Number of Units in Package 3160
Package 3 Height77.000 cm
Package 3 Width80.000 cm
Package 3 Length60.000 cm
Package 3 Weight174.740 kg
Contractual warranty
Warranty (in months)18

⚡ Key Features

  • 65 A AC-3 rated — suits up to a 30 kW squirrel-cage induction motor at 415V for direct-on-line (DOL) starting and running.
  • 24V DC coil — connects directly to pushbutton station, PLC digital output, or timer relay; suitable for standard 50Hz Indian industrial control circuits.
  • 3 Poles main contacts with silver-alloy (AgSnO₂) tips — rated for AC-3 duty (DOL motor starting/stopping); low contact resistance reduces heat at rated current.
  • Main contacts rated up to 440V AC — compatible with 415V AC three-phase Indian supply and 480V AC North American systems.
  • TeSys D series — world-standard contactor footprint; clip-on LA1D/LA4D auxiliary contact blocks and accessories attach without tools; compatible with TeSys LRD overload relays for direct-mount DOL starters.
  • Manufactured to IEC 60947-4-1 / IS 13947-4-1 — complies with the applicable Indian BIS and IEC international standards for this product category.
  • BIS certified, CE marked, RoHS compliant — meets Indian regulatory requirements for use in government, commercial, and industrial electrical installations.
  • Genuine authorised Schneider Electric product — sourced directly from the official distribution network with full manufacturer traceability and warranty.
  • GST invoice provided for India orders — valid for corporate procurement, government project orders, and public tender supply via myelectric.in.
  • Worldwide export available — UAE, Singapore, UK, USA, Sri Lanka & more. Contact +91 94814 00316 for bulk pricing and international shipping.

🔗 Compatible Products & Accessories

The following genuine accessories and compatible devices are designed to work with this product. Contact myelectric.in for pricing and availability:

GV3G264LAD9R3LAD4CMLAD9ET1SLAD4T3BLADN22LAD4D3ULADN11LADN20LADT2LADN40LAD6K10BLADN31LADN02LADT0LADS2LADR2LADR0LADN04LADN13LADR4LADT4

❓ Frequently Asked Questions

Q: Is the LC1D65ABD rated 65 A for AC-3 motor duty or AC-1 resistive duty?

A: The 65 A rating of this Schneider Electric contactor applies to AC-3 duty (squirrel cage motor starting and running). For AC-1 (resistive/non-inductive) loads, the current can be up to ~1.3× the AC-3 rating. AC-4 (plugging/reversing) requires significant de-rating — consult the Schneider Electric selection table.

Q: The LC1D65ABD has a coil voltage of 24V DC — what control supply is needed?

A: This Schneider Electric device requires a 24V DC control supply connected to the coil terminals (A1 and A2). For DC coils, observe polarity where marked. DC coils produce no inrush and are preferred for PLC output cards. Always fit a surge suppressor across the coil when switching with a PLC or solid-state relay.

Q: What circuit can the 3 NO (Normally Open) contacts of the LC1D65ABD switch at 440V AC?

A: The 3 NO (Normally Open) contacts on the LC1D65ABD are rated for switching at up to 440V AC. These auxiliary contacts are typically used for: (1) indication lamps and buzzers, (2) PLC input feedback to confirm device state, (3) interlocking with other contactors or relays in control circuits. Check the current rating of the auxiliary contact (typically 10A at 250V AC) — do not use for power load switching.

Q: What is the electrical and mechanical life of the LC1D65ABD?

A: Schneider Electric contactors are rated for millions of operations: typically 10–30 million mechanical operations and 1–3 million electrical operations at rated current and voltage (AC-3 duty). High-frequency switching applications (>10 operations/hour) require checking the specific thermal capacity of the contactor for continuous duty without overheating.

Q: Can the LC1D65ABD be used for reversing duty (forward/reverse motor control)?

A: Contactors used for reversing must be wired with two contactors interlocked so only one can energise at a time. The Schneider Electric series provides mechanical interlock kits that physically prevent both contactors from closing simultaneously — mandatory for reversing and brake applications to prevent phase-to-phase short circuits.

Customer Reviews