33191 | 1 IDENTIFIED RONIS LOCK EL24153 WITH 2 K - Schneider Electric
33191 | 1 IDENTIFIED RONIS LOCK EL24153 WITH 2 K - Schneider Electric Original price was: ₹18,120.00.Current price is: ₹9,603.60. Excl. GST
Back to products
LC1D386FLS207 | CONTACTOR TESYS LC1D 3P AC3 440V 38 A CO - Schneider Electric
LC1D386FLS207 | CONTACTOR TESYS LC1D 3P AC3 440V 38 A CO - Schneider Electric Original price was: ₹20,670.00.Current price is: ₹9,301.50. Excl. GST

RM22UA33MR | OVERVOLTAGE CONTROL RELAY RM22-UA – RANG – Schneider Electric

SKU: RM22UA33MR

Original price was: ₹14,106.00.Current price is: ₹6,488.76. Excl. GST

In stock

In stock

17 People watching this product now!

Order protection

Buy with complete confidence.

We back each order with genuine supply, on-time dispatch and GST or commercial invoicing as required.

Buyer protection on every order
Global DeliveryShipped pan-India and to export markets.
On-Time DeliveryPacked and dispatched on schedule.
100% OriginalFrom brand-authorised channels only.
GST InvoiceCompliant, ITC-ready tax invoice.
Secure PaymentEncrypted, trusted payment gateways.
Also included Dedicated account manager Technical support Bulk & business pricing 3-day replacement

Looking for the RM22UA33MR | OVERVOLTAGE CONTROL RELAY RM22-UA – RANG? This genuine Schneider Electric relay from the Harmony Control Relays range is built for motor control and switching, combining proven reliability with full compliance to applicable IEC/IS standards. Key ratings include IP20 (terminals). Order part number RM22UA33MR from myelectric.in — a trusted Schneider Electric supplier offering competitive pricing, GST billing, and shipping across India and overseas.

📋 Technical Specifications

Product
BrandSchneider Electric
Part Number / SKURM22UA33MR
CategoryRelay
Main
Range of productHarmony Control Relays
Relay typeVoltage control relay
Product or component typeVoltage control relay
Network number of phases1 phase
Supply circuit typeDC
Relay nameRM22UA
Relay monitored parametersUndervoltage and overvoltage in window mode
Overvoltage or undervoltage detection
time delayAdjustable 0.1…30 s, +/- 10 % of the full scale value Tt- time delay upon fault
Switching capacity in VA2000 VA
Measurement range15…500 V AC/DC
Contacts type and composition2 C/O
Complementary
Reset time1500 ms at maximum voltage
Maximum switching voltage250 V AC
Minimum switching current10 mA at 5 V DC
Maximum switching current8 A AC
Supply voltage limits20.4…264 V AC/DC
Power consumption in VA3.5 VA AC
Maximum power consumption in W1.5 W DC
Immunity to microbreaks10 ms
Resistance across terminals150 kOhm at E2-M terminals
300 kOhm at E1-M terminals
500 kOhm at E3-M terminals
Output contacts2 C/O
nominal output current8 A
Hysteresis3 % fixed of full scale for window mode
5…50 % adjustable of threshold setting
delay at power up600 ms
Maximum measuring cycle100 ms measurement cycle as true rms value
Repeat accuracy+/- 0.5 % for input and measurement circuit
+/- 2 % for time delay
Measurement error< 1 % over the whole range with voltage variation
0.05 %/°C with temperature variation
Response time<= 500 ms
Insulation resistance> 100 MOhm at 500 V DC
Overvoltage categoryIII conforming to IEC 60664-1
InsulationBetween supply and measurement
Connections – terminalsScrew terminals, 2 x 0.5…2 x 2.5 mm² (AWG 20…AWG 14) solid without cable end
Screw terminals, 2 x 0.2…2 x 1.5 mm² (AWG 24…AWG 16) flexible with cable end
Screw terminals, 1 x 0.5…1 x 3.3 mm² (AWG 20…AWG 12) solid without cable end
Screw terminals, 1 x 0.2…1 x 2.5 mm² (AWG 24…AWG 14) flexible with cable end
Tightening torque0.6…1 N.m conforming to IEC 60947-1
Housing materialPolycarbonate
Mounting support35 mm DIN rail conforming to IEC 60715
Electrical durability100000 cycles
Mechanical durability10000000 cycles
Utilisation categoryAC-15 conforming to IEC 60947-5-1
DC-13 conforming to IEC 60947-5-1
AC-1 conforming to IEC 60947-4-1
DC-1 conforming to IEC 60947-4-1
[Un] rated nominal voltage24…240 V AC/DC 50/60 Hz, non self-powered
Safety reliability dataMTTFd = 308.2 years
B10d = 290000
Contacts materialCadmium free
Control typeWith test button
Width22.5 mm
Product weight0.11 kg
Environment
Electromagnetic compatibilityImmunity for residential, commercial and light-industrial environments conforming to IEC 61000-6-1
Immunity for industrial environments conforming to IEC 61000-6-2
Emission standard for residential, commercial and light-industrial environments conforming to IEC 61000-6-3
Emission standard for industrial environments conforming to IEC 61000-6-4
Electrostatic discharge – test level: 6 kV level 3 (contact discharge) conforming to IEC 61000-4-2
Electrostatic discharge – test level: 8 kV level 3 (air discharge) conforming to IEC 61000-4-2
Radiated radio-frequency electromagnetic field immunity test – test level: 10 V/m level 3 conforming to IEC 61000-4-3
Electrical fast transient/burst immunity test – test level: 4 kV level 4 (direct) conforming to IEC 61000-4-4
Electrical fast transient/burst immunity test – test level: 2 kV level 4 (capacitive coupling) conforming to IEC 61000-4-4
Surge immunity test – test level: 4 kV level 4 (common mode) conforming to IEC 61000-4-5
Surge immunity test – test level: 2 kV level 4 (differential mode) conforming to IEC 61000-4-5
Conducted and radiated emissions class B group 1 conforming to CISPR 11
Conducted and radiated emissions class B conforming to CISPR 22
Ambient air temperature for operation-20…50 °C at 60 Hz
-20…60 °C at 50 Hz
StandardsIEC 60255-1
Product certificationsRCM
UL
EAC
CSA
CE
GL
CCC
Ambient air temperature for storage-40…70 °C
Relative humidity93…97 % at 25…55 °C conforming to IEC 60068-2-30
Vibration resistance0.075 mm (f= 10…58.1 Hz) not in operation conforming to IEC 60068-2-6
1 gn (f= 10…58.1 Hz) not in operation conforming to IEC 60068-2-6
0.035 mm (f= 58.1…150 Hz) in operation conforming to IEC 60068-2-6
0.5 gn (f= 58.1…150 Hz) in operation conforming to IEC 60068-2-6
Shock resistance15 gn (duration = 11 ms) for not in operation conforming to IEC 60068-2-27
5 gn (duration = 11 ms) for in operation conforming to IEC 60068-2-27
IP degree of protectionIP20 (terminals) conforming to IEC 60529
IP40 (housing) conforming to IEC 60529
IP50 (front panel) conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Dielectric test voltage2.5 kV, 1 min AC 50 Hz conforming to IEC 60255-27
Packing Units
Unit Type of Package 1PCE
Number of Units in Package 11
Package 1 Height2.600 cm
Package 1 Width8.200 cm
Package 1 Length9.500 cm
Package 1 Weight122.000 g
Unit Type of Package 2S02
Number of Units in Package 240
Package 2 Height15.000 cm
Package 2 Width30.000 cm
Package 2 Length40.000 cm
Package 2 Weight5.390 kg
Contractual warranty
Warranty (in months)18

⚡ Key Features

  • Manufactured to IEC 60947-5-1 — complies with the applicable Indian BIS and IEC international standards for this product category.
  • BIS certified, CE marked, RoHS compliant — meets Indian regulatory requirements for use in government, commercial, and industrial electrical installations.
  • Genuine authorised Schneider Electric product — sourced directly from the official distribution network with full manufacturer traceability and warranty.
  • GST invoice provided for India orders — valid for corporate procurement, government project orders, and public tender supply via myelectric.in.
  • Worldwide export available — UAE, Singapore, UK, USA, Sri Lanka & more. Contact +91 94814 00316 for bulk pricing and international shipping.

❓ Frequently Asked Questions

Q: Can the RM22UA33MR relay be mounted on a DIN rail socket for easy replacement?

A: This Schneider Electric relay typically requires direct panel or DIN rail wiring. For applications requiring frequent relay replacement, consider the plug-in relay variant of this series with a matching socket base.

Q: How do I test the RM22UA33MR relay in the field without a signal source?

A: Most Schneider Electric relays can be manually forced using the test button (if fitted) — this mechanically closes the relay contacts without energising the coil, allowing functional testing of the controlled circuit. For coil testing, use a multimeter to measure coil resistance (typically 500–2000Ω for AC coils at rated voltage) and compare with datasheet values.

Customer Reviews