5ST3730 | Pin busbar touch-safe, 10 mm2 1-phase, 214 mm long can be cut, with end caps - Siemens
5ST3730 | Pin busbar touch-safe, 10 mm2 1-phase, 214 mm long can be cut, with end caps - Siemens Original price was: ₹1,845.00.Current price is: ₹848.70. Excl. GST
Back to products
Placeholder
3RT19561CF00 | Surge suppressor (RC element) for 3RT1 S6, S10, S12 with screw terminal (drive) 400 ... 600 V AC Siemens Original price was: ₹3,305.00.Current price is: ₹1,454.20. Excl. GST

3RU29163AA01 | standalone assembly support for 3RU21/3RB30/3RB31/3RR2 Size S00 Standalone installation Main circuit: Screw Auxiliary circuit: Siemens

SKU: 3RU29163AA01

Original price was: ₹1,355.00.Current price is: ₹623.30. Excl. GST

Out of stock

Out of stock

10 People watching this product now!

Order protection

Buy with complete confidence.

We back each order with genuine supply, on-time dispatch and GST or commercial invoicing as required.

Buyer protection on every order
Global DeliveryShipped pan-India and to export markets.
On-Time DeliveryPacked and dispatched on schedule.
100% OriginalFrom brand-authorised channels only.
GST InvoiceCompliant, ITC-ready tax invoice.
Secure PaymentEncrypted, trusted payment gateways.
Also included Dedicated account manager Technical support Bulk & business pricing 3-day replacement

The Siemens 3RU29163AA01 is an overload relay, engineered for motor control and switching in demanding Indian and international installations. Buy the 3RU29163AA01 | standalone assembly support for 3RU21/3RB30/3RB31/3RR2 Size S00 Standalone installation Main circuit: Screw Auxiliary circuit: Siemens online at myelectric.in with GST invoice, genuine-product assurance, and fast delivery across India — bulk and worldwide export enquiries welcome.

📋 Technical Specifications

ParameterValue
BrandSiemens
Part Number / SKU3RU29163AA01
CategoryOverload Relay
Phase-Loss SensitivityYes — differential bimetal mechanism
Reset ModeManual / Automatic (selectable)
Auxiliary Contacts1 NO + 1 NC
MountingDirect mounting on matching contactor
Rated Frequency50/60 Hz
StandardIEC 60947-4-1 / IS 13947-4-1
CertificationsBIS certified, CE, cULus (select models)

⚡ Key Features

  • Bimetal thermal element with phase-loss sensitivity — independently monitors each phase; trips if any phase carries more than ~115% of the set current, or on complete phase failure.
  • Normally open (NO) and normally closed (NC) auxiliary contacts built in — NO contact wired to motor run indicator; NC contact wired to PLC fault input or motor starter stop circuit.
  • Manufactured to IEC 60947-4-1 / IS 13947-4-1 — complies with the applicable Indian BIS and IEC international standards for this product category.
  • BIS certified, CE, cULus (select models) — meets Indian regulatory requirements for use in government, commercial, and industrial electrical installations.
  • Genuine authorised Siemens product — sourced directly from the official distribution network with full manufacturer traceability and warranty.
  • GST invoice provided for India orders — valid for corporate procurement, government project orders, and public tender supply via myelectric.in.
  • Worldwide export available — UAE, Singapore, UK, USA, Sri Lanka & more. Contact +91 94814 00316 for bulk pricing and international shipping.

❓ Frequently Asked Questions

Q: How do I set the 3RU29163AA01 to protect a motor without causing nuisance trips on starting?

A: Set the thermal overload dial to the motor’s nameplate full-load current (FLC). For star-delta starters, set the overload relay to 58% of motor FLC (line current in delta = FLC × 0.58). Allow 10 trips for the relay’s thermal memory to stabilise before adjusting the setting.

Q: Does the 3RU29163AA01 provide single-phase (phase loss) protection?

A: Siemens thermal overload relays include single-phase sensitivity: if one phase is lost, the remaining phases carry higher current, causing the bimetal to heat and trip within the specified time. For critical motors, add a dedicated phase-loss relay for faster response independent of load — overload relay phase-loss protection is load-dependent and may take minutes to trip at light load.

Q: What is the difference between an Overload Relay and a standard MCB — and why use the 3RU29163AA01?

A: A standard MCB protects against overload and short-circuit only. An Overload Relay provides thermal overload protection calibrated to motor FLC, protecting the motor from sustained overloads that would destroy windings before a standard MCB trips. Choose the 3RU29163AA01 when the application specifically requires overload relay characteristics.