Placeholder
3UA5200-2A | Thermal Overload Relay 10 - 16 A, Contactor Mounting, Manual Reset, Suitable For 3TF32/33 Contactor - Siemens Original price was: ₹ 4,620.00.Current price is: ₹ 2,125.20. Excl. GST
Back to products
Placeholder
3UA5500-2A | Thermal Overload Relay 10 - 16 A, Contactor Mounting, Manual Reset, Suitable For 3TF34/35,44/45 Contactor - Siemens Original price was: ₹ 7,225.00.Current price is: ₹ 3,323.50. Excl. GST

3UA5200-2C | Thermal Overload Relay 16 – 25 A, Contactor Mounting, Manual Reset, Suitable For 3TF32/33 Contactor – Siemens

SKU: 3UA5200-2C

Original price was: ₹ 4,620.00.Current price is: ₹ 2,125.20. Excl. GST

My Electric Support Online · Mon–Sat 9am–6pm IST
Product enquiry
Order on WhatsApp SKU: 3UA5200-2C

Same-day dispatch · GST invoice available

19 People watching this product now!

Order protection

Buy with complete confidence.

We back each order with genuine supply, on-time dispatch and GST or commercial invoicing as required.

Buyer protection on every order
Global DeliveryShipped pan-India and to export markets.
On-Time DeliveryPacked and dispatched on schedule.
100% OriginalFrom brand-authorised channels only.
GST InvoiceCompliant, ITC-ready tax invoice.
Secure PaymentEncrypted, trusted payment gateways.
Also included Dedicated account manager Technical support Bulk & business pricing 3-day replacement

The Siemens 3UA5200-2C is an overload relay, engineered for motor control and switching in demanding Indian and international installations. Key ratings include 16–25 A. Buy the 3UA5200-2C | Thermal Overload Relay 16 – 25 A, Contactor Mounting, Manual Reset, Suitable For 3TF32/33 Contactor online at myelectric.in with GST invoice, genuine-product assurance, and fast delivery across India — bulk and worldwide export enquiries welcome.

📋 Technical Specifications

ParameterValue
BrandSiemens
Part Number / SKU3UA5200-2C
CategoryOverload Relay
Contact Configuration2 CO (Changeover)
Current Rating16–25 A
Phase-Loss SensitivityYes — differential bimetal mechanism
Reset ModeManual / Automatic (selectable)
Auxiliary Contacts1 NO + 1 NC
MountingDirect mounting on matching contactor
Rated Frequency50/60 Hz
StandardIEC 60947-4-1 / IS 13947-4-1
CertificationsBIS certified, CE, cULus (select models)

⚡ Key Features

  • Adjustable current range 16–25 A — set to the motor nameplate FLC for accurate overload detection; range covers multiple motor sizes from a single relay model.
  • Bimetal thermal element with phase-loss sensitivity — independently monitors each phase; trips if any phase carries more than ~115% of the set current, or on complete phase failure.
  • Normally open (NO) and normally closed (NC) auxiliary contacts built in — NO contact wired to motor run indicator; NC contact wired to PLC fault input or motor starter stop circuit.
  • Manual/automatic reset selectable — set to manual for attended machinery requiring operator acknowledgement; auto-reset for unattended remote installations.
  • Manufactured to IEC 60947-4-1 / IS 13947-4-1 — complies with the applicable Indian BIS and IEC international standards for this product category.
  • BIS certified, CE, cULus (select models) — meets Indian regulatory requirements for use in government, commercial, and industrial electrical installations.
  • Genuine authorised Siemens product — sourced directly from the official distribution network with full manufacturer traceability and warranty.
  • GST invoice provided for India orders — valid for corporate procurement, government project orders, and public tender supply via myelectric.in.
  • Worldwide export available — UAE, Singapore, UK, USA, Sri Lanka & more. Contact +91 94814 00316 for bulk pricing and international shipping.

❓ Frequently Asked Questions

Q: How do I set the 16–25 A adjustable range on the 3UA5200-2C for my motor?

A: Turn the setting dial to the motor’s nameplate full-load current (FLC) — the FLC must fall within the 16–25 A range of this device. Setting it at the motor FLC (not the maximum of the range) gives correct overload trip timing while still riding through normal starting inrush. If the motor FLC is outside this range, select the adjacent rating in the same series.

Q: What does the 2 CO (Changeover) contact configuration on the 3UA5200-2C mean?

A: CO (Change Over) contacts switch between two circuits — the common terminal connects to either NO or NC depending on the device state. Used for dual-purpose indication or reversing circuits.

Q: How do I set the 3UA5200-2C to protect a motor without causing nuisance trips on starting?

A: Set the thermal overload dial to the motor’s nameplate full-load current (FLC) — ensure the FLC is within the 16–25 A range of this relay. For star-delta starters, set the overload relay to 58% of motor FLC (line current in delta = FLC × 0.58). Allow 10 trips for the relay’s thermal memory to stabilise before adjusting the setting.

Q: Does the 3UA5200-2C provide single-phase (phase loss) protection?

A: Siemens thermal overload relays include single-phase sensitivity: if one phase is lost, the remaining phases carry higher current, causing the bimetal to heat and trip within the specified time. For critical motors, add a dedicated phase-loss relay for faster response independent of load — overload relay phase-loss protection is load-dependent and may take minutes to trip at light load.

Q: What is the difference between an Overload Relay and a standard MCB — and why use the 3UA5200-2C?

A: A standard MCB protects against overload and short-circuit only. An Overload Relay provides thermal overload protection calibrated to motor FLC, protecting the motor from sustained overloads that would destroy windings before a standard MCB trips. Choose the 3UA5200-2C when the application specifically requires overload relay characteristics.