5SY72638CC Betagard MCB 63 A, 2 Pole, 15 kA, D-Curve Siemens g cn01 xx 01890i
5SY72208CC | Betagard MCB 20 A, 2 Pole, 15 kA, D-Curve - Siemens Original price was: ₹1,825.00.Current price is: ₹839.50. Excl. GST
Back to products
5SY72638CC Betagard MCB 63 A, 2 Pole, 15 kA, D-Curve Siemens g cn01 xx 01890i
5SY72328CC | Betagard MCB 32 A, 2 Pole, 15 kA, D-Curve - Siemens Original price was: ₹1,825.00.Current price is: ₹839.50. Excl. GST

5SY72258CC | Betagard MCB 25 A, 2 Pole, 15 kA, D-Curve – Siemens

SKU: 5SY72258CC

Original price was: ₹1,825.00.Current price is: ₹839.50. Excl. GST

Out of stock

Out of stock

12 People watching this product now!

Order protection

Buy with complete confidence.

We back each order with genuine supply, on-time dispatch and GST or commercial invoicing as required.

Buyer protection on every order
Global DeliveryShipped pan-India and to export markets.
On-Time DeliveryPacked and dispatched on schedule.
100% OriginalFrom brand-authorised channels only.
GST InvoiceCompliant, ITC-ready tax invoice.
Secure PaymentEncrypted, trusted payment gateways.
Also included Dedicated account manager Technical support Bulk & business pricing 3-day replacement

Sourced through authorised channels, the Siemens 5SY72258CC miniature circuit breaker (mcb) delivers dependable performance for reliable circuit protection and isolation. Key ratings include 25 A, 2 Poles. myelectric.in stocks the 5SY72258CC | Betagard MCB 25 A, 2 Pole, 15 kA, D-Curve for contractors, panel builders, and project buyers — buy online with GST invoice, or request a bulk quote for domestic supply and export to UAE, Singapore, UK, USA, Sri Lanka and more.

📋 Technical Specifications

ParameterValue
BrandSiemens
Part Number / SKU5SY72258CC
CategoryMiniature Circuit Breaker (MCB)
Current Rating25 A
Poles2 Poles
Breaking Capacity15 kA
Rated Voltage230/400V AC
Rated Frequency50/60 Hz
Trip MechanismThermal-magnetic (bimetal overload + electromagnetic short-circuit)
Mounting35mm DIN rail (EN 60715)
Width36 mm (2 × 18mm modules)
Electrical Endurance≥ 20,000 operating cycles (per IEC 60898-1)
Pollution Degree3 (per IEC 60664-1)
StandardIS 8828 / IEC 60898-1 (residential) and IEC 60947-2 (industrial)
CertificationsBIS certified, CE, cULus (select models)

⚡ Key Features

  • Protects circuits at 25 A with 15 kA short-circuit breaking capacity — rated for industrial sub-distribution boards with high prospective fault currents.
  • 2 Poles — protects a single-phase circuit, switching both live and neutral; fits standard 35mm DIN rail in distribution boards.
  • Thermal-magnetic trip mechanism — bimetal element trips on sustained overload, instantaneous magnetic trip on short-circuit; two independent protection functions in one compact module.
  • Manufactured to IS 8828 / IEC 60898-1 (residential) and IEC 60947-2 (industrial) — complies with the applicable Indian BIS and IEC international standards for this product category.
  • BIS certified, CE, cULus (select models) — meets Indian regulatory requirements for use in government, commercial, and industrial electrical installations.
  • Genuine authorised Siemens product — sourced directly from the official distribution network with full manufacturer traceability and warranty.
  • GST invoice provided for India orders — valid for corporate procurement, government project orders, and public tender supply via myelectric.in.
  • Worldwide export available — UAE, Singapore, UK, USA, Sri Lanka & more. Contact +91 94814 00316 for bulk pricing and international shipping.

❓ Frequently Asked Questions

Q: What load can the 5SY72258CC protect at its rated 25 A?

A: The 5SY72258CC is rated to carry and protect circuits up to 25 A continuously. For motor loads, ensure the full-load current (FLC) of the motor does not exceed this rating. For resistive loads (heaters, lighting), the 25 A rating is used directly. Derate by 20% for ambient temperatures above 40°C.

Q: What does the 15 kA breaking capacity on the 5SY72258CC mean in practice?

A: Breaking capacity (15 kA) is the maximum prospective short-circuit current the 5SY72258CC can safely interrupt without damage. Before installing, verify that the prospective fault level at the installation point does not exceed 15 kA — this is checked using a fault level calculation or from the upstream transformer impedance data. Installing a breaker with insufficient breaking capacity is a serious safety violation.

Q: Is the 5SY72258CC suitable for both single-phase and three-phase systems?

A: The 5SY72258CC is a 2 poles device for single-phase circuits. For three-phase circuits, use a 3-pole or 4-pole MCB of the same series.

Q: Can the 5SY72258CC be DIN rail mounted in any standard distribution board?

A: Yes. This Siemens MCB uses the standard 35mm EN 60715 DIN rail and 17.5mm module width, making it compatible with all major brand distribution boards and enclosures. Terminal capacity accommodates both rigid and flexible conductors up to the rated cross-section.

Q: What happens when the 5SY72258CC trips — how do I identify and reset it?

A: When the 5SY72258CC trips on fault, the handle moves to a midway position (between ON and OFF), distinctly visible from a distance. To reset: (1) identify and rectify the fault, (2) push the handle fully to OFF, (3) then switch back to ON. Never force-reset without investigating the fault cause.