65299 | MICROLOGIC 5.0 FOR DRAWOUT BREAKER MASTE - Schneider Electric
65299 | MICROLOGIC 5.0 FOR DRAWOUT BREAKER MASTE - Schneider Electric Original price was: ₹23,180.00.Current price is: ₹12,285.40. Excl. GST
Back to products
65301 | MICROLOGIC 5.0 FOR FIXED MASTERPACT NW - Schneider Electric
65301 | MICROLOGIC 5.0 FOR FIXED MASTERPACT NW - Schneider Electric Original price was: ₹23,180.00.Current price is: ₹12,285.40. Excl. GST

65300 | MICROLOGIC 2.0 FOR FIXED MASTERPACT NW – Schneider Electric

SKU: 65300

Original price was: ₹16,740.00.Current price is: ₹8,872.20. Excl. GST

Dispatch By : 15 Weeks

Dispatch By : 15 Weeks

11 People watching this product now!

Order protection

Buy with complete confidence.

We back each order with genuine supply, on-time dispatch and GST or commercial invoicing as required.

Buyer protection on every order
Global DeliveryShipped pan-India and to export markets.
On-Time DeliveryPacked and dispatched on schedule.
100% OriginalFrom brand-authorised channels only.
GST InvoiceCompliant, ITC-ready tax invoice.
Secure PaymentEncrypted, trusted payment gateways.
Also included Dedicated account manager Technical support Bulk & business pricing 3-day replacement

Specifications

Main
RangeMasterPact
Range of productMasterPact NW
Product or component typeControl unit
Trip unit nameMicroLogic 2.0
Trip unit technologyElectronic
Range compatibilityMasterpact NW08…40
Masterpact NW40b…63
Device applicationDistribution
Number of poles3P
4P
Protected poles description4t
3t
3t + N/2
Trip unit protection functionsBasic protection
Protection typefor overload protection (long time)
for instantaneous short-circuit protection
Trip unit rating800 A at 50 °C
1000 A at 50 °C
1250 A at 50 °C
1600 A at 50 °C
2000 A at 50 °C
2500 A at 50 °C
3200 A at 50 °C
4000 A at 50 °C
5000 A at 50 °C
6300 A at 50 °C
Network typeAC
Network frequency50/60 Hz
Circuit breaker mounting modeFixed
Complementary
Long-time pick-up adjustment type Ir (thermal protection)Adjustable 9 settings
[Ir] long-time protection pick-up adjustment range0.4…1 x In
Long-time protection delay adjustment type trAdjustable 9 settings
[tr] long-time protection delay adjustment range0.7…16.6 s at 7.2 x Ir
0.5…24 s at 6 x Ir
12.5…600 s at 1.5 x Ir
Thermal memory20 mn
Instantaneous protection pick-up adjustment type IiAdjustable 9 settings
[Ii] instantaneous protection pick-up adjustment range1.5…10 x Ir
Earth-leakage protectionWithout
Zone selective interlocking ZSIWithout
Local signalling3 LEDs (red) for electrical fault
1 LED (red) for internal error
Environment
Ambient air temperature for operation-25…70 °C
Ambient air temperature for storage-50…85 °C
Packing Units
Unit Type of Package 1PCE
Number of Units in Package 11
Package 1 Height6.8 cm
Package 1 Width8.0 cm
Package 1 Length21.5 cm
Package 1 Weight318.0 g
Contractual warranty
Warranty (in months)18

Customer Reviews