C10V35E040 | NSX100HB1 75kA AC 3P 40A 5.2E - Schneider Electric
C10V35E040 | NSX100HB1 75kA AC 3P 40A 5.2E - Schneider Electric Original price was: ₹381,160.00.Current price is: ₹172,474.90. Excl. GST
Back to products
C10V36E040 | NSX100HB1 75kA AC 3P 40A 6.2E - Schneider Electric
C10V36E040 | NSX100HB1 75kA AC 3P 40A 6.2E - Schneider Electric Original price was: ₹461,660.00.Current price is: ₹208,901.15. Excl. GST

C10V35E100 | NSX100HB1 75kA AC 3P 100A 5.2E – Schneider Electric

SKU: C10V35E100

Original price was: ₹419,310.00.Current price is: ₹189,737.78. Excl. GST

Dispatch By : 10 Weeks

Dispatch By : 10 Weeks

16 People watching this product now!

Order protection

Buy with complete confidence.

We back each order with genuine supply, on-time dispatch and GST or commercial invoicing as required.

Buyer protection on every order
Global DeliveryShipped pan-India and to export markets.
On-Time DeliveryPacked and dispatched on schedule.
100% OriginalFrom brand-authorised channels only.
GST InvoiceCompliant, ITC-ready tax invoice.
Secure PaymentEncrypted, trusted payment gateways.
Also included Dedicated account manager Technical support Bulk & business pricing 3-day replacement

Specifications

Main
RangeComPacT
Product nameComPacT NSX
Device short nameNSX100HB1
Product or component typeCircuit breaker
Device applicationDistribution
Poles description3P
Protected poles description3D
[In] rated current100 A at 40 °C
[Ue] rated operational voltage690 V AC 50/60 Hz
Network typeAC
Network frequency50/60 Hz
Suitability for isolationYes conforming to EN/IEC 60947-2
Utilisation categoryCategory A
Breaking capacity85 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
80 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
75 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity codeHB1 75 kA 690 V AC
Trip unit nameMicroLogic 5.2 E
Trip unit technologyElectronic
Trip unit protection functionsLSI
Control typeToggle
Circuit breaker mounting modeFixed
Complementary
[Ui] rated insulation voltage800 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage8 kV
[Ics] rated service breaking capacity85 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
80 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
75 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Mechanical durability20000 cycles
Electrical durability20000 cycles at 440 V In/2
10000 cycles at 440 V In
10000 cycles at 690 V In/2
5000 cycles at 690 V In
Power dissipation per pole4.7 W
Mounting supportBackplate
Mounting positionHorizontal and vertical
Flat on the back
Upside connectionFront
Downside connectionFront
Connection pitch35 mm
Protection typeL : for overload protection (long time)
S : for short time short-circuit protection
I : for instantaneous short-circuit protection
Trip unit rating100 A at 40 °C
Long-time pick-up adjustment type Ir (thermal protection)Adjustable 9 settings
[Ir] long-time protection pick-up adjustment range40…100 A
Long-time protection delay adjustment type trAdjustable
[tr] long-time delay adjustment range15…400 s at 1.5 x Ir
0.5…16 s at 6 x Ir
0.35…11 s at 7.2 x Ir
Thermal memory20 minutes before and after tripping
Short-time protection pick-up adjustment type IsdAdjustable 9 settings
[Isd] Short-time protection pick-up adjustment range1.5…10 x Ir
Short-time protection delay adjustment type tsdAdjustable 5 settings
[tsd] short-time delay adjustment range0…0.4 s I²t=off
0.1…0.4 s I²t=on
Instantaneous protection pick-up adjustment type IiAdjustable
[Ii] instantaneous protection pick-up adjustment range1.5…15 x In
Earth-leakage protectionWithout
Zone selective interlocking ZSIWith
Number of slots5 slot(s)
Local signallingFlashing LED (green) for ready to operate
LED 105 % Ir (red) for overload
LED 90 % Ir (orange) for overload
Display typeLCD display
Type of measurementEnergy meter
Communication of dataMaintenance indicators
Maximeters/minimeters
Protection and alarm settings
Time-stamped histories and event tables
Energy metering
Demand current and power
Instantaneous and demand values
Power quality
Width (W)105 mm
Height (H)161 mm
Depth (D)86 mm
Net weight2.05 kg
Environment
StandardsEN/IEC 60947-2
Overvoltage categoryIII
Electrical shock protection classClass II on front face
Pollution degree3 conforming to IEC 60664-1
IP degree of protectionIP40 conforming to IEC 60529
IK degree of protectionIK07 conforming to IEC 62262
Ambient air temperature for operation-25…70 °C
Ambient air temperature for storage-40…85 °C
Relative humidity0…95 %
Operating altitude0…2000 m without derating
2000 m…5000 m with derating
Packing Units
Unit Type of Package 1PCE
Number of Units in Package 11
Package 1 Height11.000 cm
Package 1 Width14.000 cm
Package 1 Length20.000 cm
Package 1 Weight1.992 kg
Unit Type of Package 2S03
Number of Units in Package 24
Package 2 Height30.000 cm
Package 2 Width30.000 cm
Package 2 Length40.000 cm
Package 2 Weight8.388 kg
Unit Type of Package 3P12
Number of Units in Package 332
Package 3 Height45.000 cm
Package 3 Width80.000 cm
Package 3 Length120.000 cm
Package 3 Weight79.104 kg
Logistical informations
Country of originPL
Contractual warranty
Warranty (in months)18

Customer Reviews