C40V36E400 | NSX400HB1 75kA AC 3P 400A 6.3E - Schneider Electric
C40V36E400 | NSX400HB1 75kA AC 3P 400A 6.3E - Schneider Electric Original price was: ₹623,520.00.Current price is: ₹282,142.80. Excl. GST
Back to products
C40V42D400 | NSX400HB1 75kA AC 4P 400A 2.3 - Schneider Electric
C40V42D400 | NSX400HB1 75kA AC 4P 400A 2.3 - Schneider Electric Original price was: ₹422,260.00.Current price is: ₹191,072.65. Excl. GST

C40V36M320 | NSX400HB1 75kA AC 3P 320A 6.3EM – Schneider Electric

SKU: C40V36M320

Original price was: ₹623,520.00.Current price is: ₹282,142.80. Excl. GST

Dispatch By : 7 Weeks

Dispatch By : 7 Weeks

18 People watching this product now!

Order protection

Buy with complete confidence.

We back each order with genuine supply, on-time dispatch and GST or commercial invoicing as required.

Buyer protection on every order
Global DeliveryShipped pan-India and to export markets.
On-Time DeliveryPacked and dispatched on schedule.
100% OriginalFrom brand-authorised channels only.
GST InvoiceCompliant, ITC-ready tax invoice.
Secure PaymentEncrypted, trusted payment gateways.
Also included Dedicated account manager Technical support Bulk & business pricing 3-day replacement

Specifications

Main
RangeComPacT
Product nameComPacT NSX
Device short nameNSX400HB1
Product or component typeCircuit breaker
Device applicationDistribution
Poles description3P
Protected poles description3D
[In] rated current320 A at 65 °C
[Ue] rated operational voltage690 V AC 50/60 Hz
Network typeAC
Network frequency50/60 Hz
Suitability for isolationYes conforming to EN/IEC 60947-2
Utilisation categoryCategory A
Breaking capacity85 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
80 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
75 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity codeHB1 75 kA 690 V AC
Trip unit nameMicroLogic 6.3 E-M
Trip unit technologyElectronic
Trip unit protection functionsLSIG
Control typeToggle
Circuit breaker mounting modeFixed
Complementary
[Ui] rated insulation voltage800 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage8 kV
[Ics] rated service breaking capacity85 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
80 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
75 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Mechanical durability15000 cycles
Electrical durability12000 cycles at 440 V In/2
6000 cycles at 440 V In
6000 cycles at 690 V In/2
3000 cycles at 690 V In
Power dissipation per pole19.2 W
Mounting supportBackplate
Mounting positionHorizontal and vertical
Flat on the back
Upside connectionFront
Downside connectionFront
Connection pitch45 mm
Protection typeL : for overload protection (long time)
So : for short time short-circuit protection
I : for instantaneous short-circuit protection
G : for ground fault protection
Trip unit rating320 A at 65 °C
Motor tripping class10
30
20
5
Complementary motor protectionUnderload
Protracted starting time
Phase unbalance
Stalled rotor
Long-time pick-up adjustment type Ir (thermal protection)Adjustable 9 settings
[Ir] long-time protection pick-up adjustment range160…320 A
Long-time protection delay adjustment type trAdjustable
[tr] long-time delay adjustment range120 s at 1.5 x Ir for trip class 5
6.5 s at 6 x Ir for trip class 5
5 s at 7.2 x Ir for trip class 5
240 s at 1.5 x Ir for trip class 10
13.5 s at 6 x Ir for trip class 10
10 s at 7.2 x Ir for trip class 10
480 s at 1.5 x Ir for trip class 20
26 s at 6 x Ir for trip class 20
20 s at 7.2 x Ir for trip class 20
720 s at 1.5 x Ir for trip class 30
38 s at 6 x Ir for trip class 30
30 s at 7.2 x Ir for trip class 30
Thermal memory20 minutes before and after tripping
Short-time protection pick-up adjustment type IsdAdjustable
[Isd] Short-time protection pick-up adjustment range5…13 x Ir
Short-time protection delay adjustment type tsdFixed
Instantaneous protection pick-up adjustment type IiFixed
[Ii] instantaneous protection pick-up adjustment range4800 A
Ground-fault protection pick-up adjustment type IgAdjustable 9 settings
[Ig] ground-fault pick-up adjustment range0.6…1 x In for In = 25 A
0.3…1 x In for In = 50 A
0.2…1 x In for In > 50 A
Ig enable on/off
Ground-fault protection time delay adjustment type tgAdjustable 5 settings
[tg] Ground-fault time delay adjustment range0…0.4 s
Earth-leakage protectionWithout
Zone selective interlocking ZSIWith
Number of slots6 slot(s)
Local signallingFlashing LED (green) for ready to operate
LED 95 % Ith (red) for temperature over set point
Display typeLCD display
Type of measurementEnergy meter
Communication of dataPhase sequence
Protection and alarm settings
Maintenance indicators
Power quality
Maximeters/minimeters
Time-stamped histories and event tables
Thermal image function
Demand current and power
Energy metering
Instantaneous and demand values
Width (W)140 mm
Height (H)255 mm
Depth (D)110 mm
Net weight6.05 kg
Environment
StandardsEN/IEC 60947-2
Overvoltage categoryIII
Electrical shock protection classClass II on front face
Pollution degree3 conforming to IEC 60664-1
IP degree of protectionIP40 conforming to IEC 60529
IK degree of protectionIK07 conforming to IEC 62262
Ambient air temperature for operation-25…70 °C
Ambient air temperature for storage-40…85 °C
Relative humidity0…95 %
Operating altitude0…2000 m without derating
2000 m…5000 m with derating
Packing Units
Unit Type of Package 1PCE
Number of Units in Package 11
Package 1 Height15.2 cm
Package 1 Width15.2 cm
Package 1 Length29.2 cm
Package 1 Weight5.82 kg
Contractual warranty
Warranty (in months)18

Customer Reviews