C40W36E400 | NSX400HB2 100kA AC 3P 400A 6.3E - Schneider Electric
C40W36E400 | NSX400HB2 100kA AC 3P 400A 6.3E - Schneider Electric Original price was: $177,140.60.Current price is: $80,156.12. Excl. GST
Back to products
C40W42D250 | NSX400HB2 100kA AC 4P 250A 2.3 - Schneider Electric
C40W42D250 | NSX400HB2 100kA AC 4P 250A 2.3 - Schneider Electric Original price was: $120,044.60.Current price is: $54,320.18. Excl. GST

C40W36M320 | NSX400HB2 100kA AC 3P 320A 6.3EM – Schneider Electric

SKU: C40W36M320

Original price was: $177,140.60.Current price is: $80,156.12. Excl. GST

Dispatch By : 7 Weeks

Dispatch By : 7 Weeks

11 People watching this product now!

Order protection

Buy with complete confidence.

We back each order with genuine supply, on-time dispatch and GST or commercial invoicing as required.

Buyer protection on every order
Global DeliveryShipped pan-India and to export markets.
On-Time DeliveryPacked and dispatched on schedule.
100% OriginalFrom brand-authorised channels only.
GST InvoiceCompliant, ITC-ready tax invoice.
Secure PaymentEncrypted, trusted payment gateways.
Also included Dedicated account manager Technical support Bulk & business pricing 3-day replacement

Specifications

Main
RangeComPacT
Product nameComPacT NSX
Device short nameNSX400HB2
Product or component typeCircuit breaker
Device applicationDistribution
Poles description3P
Protected poles description3D
[In] rated current320 A at 65 °C
[Ue] rated operational voltage690 V AC 50/60 Hz
Network typeAC
Network frequency50/60 Hz
Suitability for isolationYes conforming to EN/IEC 60947-2
Utilisation categoryCategory A
Breaking capacity100 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
100 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
100 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity codeHB2 100 kA 690 V AC
Trip unit nameMicroLogic 6.3 E-M
Trip unit technologyElectronic
Trip unit protection functionsLSIG
Control typeToggle
Circuit breaker mounting modeFixed
Complementary
[Ui] rated insulation voltage800 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage8 kV
[Ics] rated service breaking capacity100 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
100 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
100 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Mechanical durability15000 cycles
Electrical durability12000 cycles at 440 V In/2
6000 cycles at 440 V In
6000 cycles at 690 V In/2
3000 cycles at 690 V In
Power dissipation per pole19.2 W
Mounting supportBackplate
Mounting positionHorizontal and vertical
Flat on the back
Upside connectionFront
Downside connectionFront
Connection pitch45 mm
Protection typeL : for overload protection (long time)
So : for short time short-circuit protection
I : for instantaneous short-circuit protection
G : for ground fault protection
Trip unit rating320 A at 65 °C
Motor tripping class30
20
5
10
Complementary motor protectionProtracted starting time
Underload
Phase unbalance
Stalled rotor
Long-time pick-up adjustment type Ir (thermal protection)Adjustable 9 settings
[Ir] long-time protection pick-up adjustment range160…320 A
Long-time protection delay adjustment type trAdjustable
[tr] long-time delay adjustment range120 s at 1.5 x Ir for trip class 5
6.5 s at 6 x Ir for trip class 5
5 s at 7.2 x Ir for trip class 5
240 s at 1.5 x Ir for trip class 10
13.5 s at 6 x Ir for trip class 10
10 s at 7.2 x Ir for trip class 10
480 s at 1.5 x Ir for trip class 20
26 s at 6 x Ir for trip class 20
20 s at 7.2 x Ir for trip class 20
720 s at 1.5 x Ir for trip class 30
38 s at 6 x Ir for trip class 30
30 s at 7.2 x Ir for trip class 30
Thermal memory20 minutes before and after tripping
Short-time protection pick-up adjustment type IsdAdjustable
[Isd] Short-time protection pick-up adjustment range5…13 x Ir
Short-time protection delay adjustment type tsdFixed
Instantaneous protection pick-up adjustment type IiFixed
[Ii] instantaneous protection pick-up adjustment range4800 A
Ground-fault protection pick-up adjustment type IgAdjustable 9 settings
[Ig] ground-fault pick-up adjustment range0.6…1 x In for In = 25 A
0.3…1 x In for In = 50 A
0.2…1 x In for In > 50 A
Ig enable on/off
Ground-fault protection time delay adjustment type tgAdjustable 5 settings
[tg] Ground-fault time delay adjustment range0…0.4 s
Earth-leakage protectionWithout
Zone selective interlocking ZSIWith
Number of slots6 slot(s)
Local signallingFlashing LED (green) for ready to operate
LED 95 % Ith (red) for temperature over set point
Display typeLCD display
Type of measurementEnergy meter
Communication of dataDemand current and power
Maintenance indicators
Thermal image function
Power quality
Maximeters/minimeters
Energy metering
Protection and alarm settings
Time-stamped histories and event tables
Phase sequence
Instantaneous and demand values
Width (W)140 mm
Height (H)255 mm
Depth (D)110 mm
Net weight6.05 kg
Environment
StandardsEN/IEC 60947-2
Overvoltage categoryIII
Electrical shock protection classClass II on front face
Pollution degree3 conforming to IEC 60664-1
IP degree of protectionIP40 conforming to IEC 60529
IK degree of protectionIK07 conforming to IEC 62262
Ambient air temperature for operation-25…70 °C
Ambient air temperature for storage-40…85 °C
Relative humidity0…95 %
Operating altitude0…2000 m without derating
2000 m…5000 m with derating
Packing Units
Unit Type of Package 1PCE
Number of Units in Package 11
Package 1 Height15.2 cm
Package 1 Width15.2 cm
Package 1 Length29.2 cm
Package 1 Weight5.82 kg
Contractual warranty
Warranty (in months)18