Placeholder
C63H46A630 | NSX630H 70kA AC 4P4D 630A 6.3A - Schneider Electric Original price was: ₹218,980.00.Current price is: ₹105,110.40. Excl. GST
Back to products

C63H47E570 | NSX630H 70kA AC 4P4D 570A 7.3E – Schneider Electric

SKU: C63H47E570

Original price was: ₹454,710.00.Current price is: ₹205,756.28. Excl. GST

Dispatch By : 5 Weeks

Dispatch By : 5 Weeks

19 People watching this product now!

Order protection

Buy with complete confidence.

We back each order with genuine supply, on-time dispatch and GST or commercial invoicing as required.

Buyer protection on every order
Global DeliveryShipped pan-India and to export markets.
On-Time DeliveryPacked and dispatched on schedule.
100% OriginalFrom brand-authorised channels only.
GST InvoiceCompliant, ITC-ready tax invoice.
Secure PaymentEncrypted, trusted payment gateways.
Also included Dedicated account manager Technical support Bulk & business pricing 3-day replacement

Specifications

Main
RangeComPacT
Product nameComPacT NSX
Device short nameNSX630H
Product or component typeEarth leakage circuit breaker
Device applicationDistribution
Poles description4P
Protected poles description4D
3D + OSN
3D + N/2
3D
Neutral positionLeft
[In] rated current570 A at 40 °C
[Ue] rated operational voltage440 V AC 50/60 Hz
Network typeAC
Network frequency50/60 Hz
Suitability for isolationYes conforming to EN/IEC 60947-2
Utilisation categoryCategory A
Breaking capacity100 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
20 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1
65 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1
20 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1
Breaking capacity codeH 70 kA 415 V AC
Trip unit nameMicroLogic 7.3 E
Trip unit technologyElectronic
Trip unit protection functionsLSIR
Control typeToggle
Circuit breaker mounting modeFixed
Complementary
[Ui] rated insulation voltage500 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage8 kV
[Ics] rated service breaking capacity100 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
70 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
65 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
50 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
11 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Mechanical durability15000 cycles
Electrical durability8000 cycles at 440 V In/2
4000 cycles at 440 V In
6000 cycles at 690 V In/2
2000 cycles at 690 V In
Power dissipation per pole55.6 W N
55.6 W L1 and L3
47.6 W L2
Mounting supportBackplate
Mounting positionHorizontal and vertical
Flat on the back
Upside connectionFront
Downside connectionFront
Connection pitch45 mm
Protection typeL : for overload protection (long time)
S : for short time short-circuit protection
I : for instantaneous short-circuit protection
R : for earth-leakage protection
Trip unit rating570 A at 40 °C
Long-time pick-up adjustment type Ir (thermal protection)Adjustable 9 settings
[Ir] long-time protection pick-up adjustment range250…570 A
Long-time protection delay adjustment type trAdjustable
[tr] long-time delay adjustment range15…400 s at 1.5 x Ir
0.5…16 s at 6 x Ir
0.35…11 s at 7.2 x Ir
Neutral protection setting0.5 x Ir (3D + N/2)
1 x Ir (4D)
No protection (3D)
Thermal memory20 minutes before and after tripping
Short-time protection pick-up adjustment type IsdAdjustable
[Isd] Short-time protection pick-up adjustment range1.5…10 x Ir
Short-time protection delay adjustment type tsdAdjustable
[tsd] short-time delay adjustment range0…0.4 s I²t=off
0.1…0.4 s I²t=on
Instantaneous protection pick-up adjustment type IiAdjustable
[Ii] instantaneous protection pick-up adjustment range1.5…12 x In
Earth-leakage protectionIntegrated
Earth-leakage protection classClass A
Earth-leakage protection sensitity adjustment type IΔnAdjustable
[IΔn] earth-leakage protection sensitivity adjustment range300 mA
500 mA
1 A
3 A
5 A
10 A
Operating modeOFF using the IΔn rotary switch
Earth-leakage protection time delay adjustement type ΔtAdjustable
[Δt] residual earth-leakage time delay adjustment0 ms
60 ms
150 ms
500 ms
1 s
Zone selective interlocking ZSIWithout
Number of slots6 slot(s)
Local signallingFlashing LED (green) for ready to operate
LED 105 % Ir (red) for overload
LED 90 % Ir (orange) for overload
Display typeLCD display
Type of measurementEnergy meter
Communication of dataTime-stamped histories and event tables
Maintenance indicators
Instantaneous and demand values
Maximeters/minimeters
Protection and alarm settings
Power quality
Energy metering
Demand current and power
Width (W)185 mm
Height (H)255 mm
Depth (D)110 mm
Net weight8.13 kg
Environment
StandardsEN/IEC 60947-2
Overvoltage categoryIV
Electrical shock protection classClass II on front face
Pollution degree3 conforming to IEC 60664-1
IP degree of protectionIP40 conforming to IEC 60529
IK degree of protectionIK07 conforming to IEC 62262
Ambient air temperature for operation-25…70 °C
Ambient air temperature for storage-40…85 °C
Relative humidity0…95 %
Operating altitude0…2000 m without derating
2000 m…5000 m with derating
Packing Units
Unit Type of Package 1PCE
Number of Units in Package 11
Package 1 Height16.800 cm
Package 1 Width25.500 cm
Package 1 Length18.500 cm
Package 1 Weight7.897 kg
Contractual warranty
Warranty (in months)18