VX4A61101Y ControlBlock Schneider Electric Image
VX4A61101Y | ControlBlock - Schneider Electric Original price was: ₹72,407.00.Current price is: ₹62,270.02. Excl. GST
Back to products
MM1102 1 Mm 2 Gang GI Metal Box Schneider Electric product placeholder
ATV340U15N4E | Atv340 1,5Kw 2Hp 400V With Ethernet Vari - Schneider Electric Original price was: ₹115,859.00.Current price is: ₹35,916.29. Excl. GST

LXM26DU15M3X | Lexium 26 Io Drive 1/3Ph 230V 1,5Kw – Schneider Electric

SKU: LXM26DU15M3X

Original price was: ₹125,650.00.Current price is: ₹51,516.50. Excl. GST

Dispatch By : 12 Weeks

Dispatch By : 12 Weeks

19 People watching this product now!

Order protection

Buy with complete confidence.

We back each order with genuine supply, on-time dispatch and GST or commercial invoicing as required.

Buyer protection on every order
Global DeliveryShipped pan-India and to export markets.
On-Time DeliveryPacked and dispatched on schedule.
100% OriginalFrom brand-authorised channels only.
GST InvoiceCompliant, ITC-ready tax invoice.
Secure PaymentEncrypted, trusted payment gateways.
Also included Dedicated account manager Technical support Bulk & business pricing 3-day replacement

Sourced through authorised channels, the Schneider Electric LXM26DU15M3X variable frequency drive (vfd) delivers dependable performance for variable-speed motor control and energy savings. Key ratings include 230V AC. myelectric.in stocks the LXM26DU15M3X | Lexium 26 Io Drive 1/3Ph 230V 1,5Kw for contractors, panel builders, and project buyers — buy online with GST invoice, or request a bulk quote for domestic supply and export to UAE, Singapore, UK, USA, Sri Lanka and more.

📋 Technical Specifications

ParameterValue
BrandSchneider Electric
Part Number / SKULXM26DU15M3X
CategoryVariable Frequency Drive (VFD)
Voltage Rating230V AC
Power Rating5 kW
Input Frequency50/60 Hz ± 5%
Protection FunctionsMotor overload, phase-loss, overcurrent, overvoltage, undervoltage
StandardIEC 61800-5-1 (safety) and IEC 61800-3 (EMC)
CertificationsBIS certified, CE marked, RoHS compliant

⚡ Key Features

  • Rated for a 5 kW motor — adjustable output frequency from near 0 to 50/60 Hz gives stepless speed control for pumps, fans, compressors, and conveyor drives.
  • Soft-start acceleration ramp — limits motor starting current to ~1.5× FLC vs. the 6–7× FLC of DOL starting; eliminates mechanical shock on gearboxes, belts, and couplings and reduces peak demand charges.
  • Built-in electronic motor protection — overload, phase-loss, overvoltage (+10%), undervoltage, and short-circuit protection without additional external relays.
  • Manufactured to IEC 61800-5-1 (safety) and IEC 61800-3 (EMC) — complies with the applicable Indian BIS and IEC international standards for this product category.
  • BIS certified, CE marked, RoHS compliant — meets Indian regulatory requirements for use in government, commercial, and industrial electrical installations.
  • Genuine authorised Schneider Electric product — sourced directly from the official distribution network with full manufacturer traceability and warranty.
  • GST invoice provided for India orders — valid for corporate procurement, government project orders, and public tender supply via myelectric.in.
  • Worldwide export available — UAE, Singapore, UK, USA, Sri Lanka & more. Contact +91 94814 00316 for bulk pricing and international shipping.

❓ Frequently Asked Questions

Q: Can the LXM26DU15M3X be used to control a 5 kW motor with soft start and variable speed?

A: Yes. This VFD is rated for a 5 kW motor load and provides stepless speed control from 0 to rated frequency (typically 0–50 Hz). The soft-start ramp eliminates mechanical shock and reduces starting current from typically 6–7× FLC to just 1–1.5× FLC. Ensure the motor cable length does not exceed the VFD manufacturer’s maximum (typically 50–100m without output filter) to avoid insulation stress.

Q: Does the LXM26DU15M3X require an input line reactor or output filter for protection?

A: For installations with poor power quality (voltage spikes, harmonics), an input line reactor (3–5% impedance) extends the LXM26DU15M3X’s life by reducing diode stress and lowering harmonic injection. An output dV/dt filter is recommended when motor cable exceeds 50m to prevent reflected wave damage to motor insulation, especially on older motors not rated for VFD use.

Q: Can the LXM26DU15M3X run a standard squirrel-cage induction motor without modification?

A: Yes — standard squirrel-cage induction motors rated for 415V 50Hz can be driven by this VFD. However, at low speeds (<20 Hz), motor cooling is reduced because the shaft-mounted fan slows down. For extended low-speed operation, fit a separately powered external cooling fan on the motor, or use a motor specified for inverter duty.

Q: Does the LXM26DU15M3X inject harmonics into the supply and is a line reactor required?

A: VFDs including the LXM26DU15M3X generate harmonic currents (primarily 5th and 7th order) due to their diode rectifier front-end. In installations where total harmonic distortion (THD) is a concern — such as facilities with sensitive medical or measurement equipment, or where multiple large drives share a common bus — a 3% or 5% impedance line reactor on the input significantly reduces harmonic injection and protects the drive’s DC bus capacitors from voltage spikes. Check if your site’s power quality specification sets a THD limit.