MVS16DA14F7 | EP MVS DA1 1600A 100KA 4P 24 VDC - Schneider Electric
$10,765.30 Original price was: $10,765.30.$6,566.83Current price is: $6,566.83. Excl. GST
MVS16T33D500 | EP MVS CB 1600A 1140V 3PD 50 VSPO manual - Schneider Electric
$9,417.07 Original price was: $9,417.07.$5,744.41Current price is: $5,744.41. Excl. GST
MVS16N3MW6L | EP MVS CB 1600A 50kA 3P MDO ET6 drawout – Schneider Electric
SKU:
MVS16N3MW6L
$7,038.59 Original price was: $7,038.59.$4,293.54Current price is: $4,293.54. Excl. GST
Dispatch By : -6615 Weeks
Dispatch By : -6615 Weeks
14
People watching this product now!
Order protection
Buy with complete confidence.
We back each order with genuine supply, on-time dispatch and GST or commercial invoicing as required.
Global DeliveryShipped pan-India and to export markets.
On-Time DeliveryPacked and dispatched on schedule.
100% OriginalFrom brand-authorised channels only.
GST InvoiceCompliant, ITC-ready tax invoice.
Secure PaymentEncrypted, trusted payment gateways.
Also included
Dedicated account manager
Technical support
Bulk & business pricing
3-day replacement
Specifications
| Main | |
|---|---|
| Range | EasyPact |
| Product name | MVS16N |
| Device short name | MVS16N |
| Product or component type | Circuit breaker |
| Device application | Distribution |
| Poles description | 3P |
| Protected poles description | 3P 3d |
| [In] rated current | 1600 A at 40 °C |
| Network type | AC |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| Breaking capacity code | N |
| Suitability for isolation | Yes conforming to IEC 60947-2 |
| Utilisation category | Category B |
| Trip unit name | ET6G |
| Trip unit technology | Electronic |
| Trip unit rating | 1600 A |
| Complementary | |
| Network frequency | 50/60 Hz |
| Control type | Manually operated |
| Mounting mode | Drawout |
| Mounting support | Rail Base plate |
| Connection position | Vertical Horizontal |
| Location of connection | Rear |
| [Ui] rated insulation voltage | 1000 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Uimp] rated impulse withstand voltage | 12 kV conforming to IEC 60947-2 |
| Circuit breaker CT rating | 1600 A |
| Breaking capacity | 50 kA Icu at 220…440 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Ics] rated service breaking capacity | 50 kA (Ics) at 220…440 V AC 50/60 Hz conforming to IEC 60947-2 |
| Mechanical durability | 20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2 |
| Electrical durability | Category B: 6000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2 Category B: 4000 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2 |
| Connection pitch | 115 mm without spreader |
| Contact position indicator | Yes |
| [Icm] rated short-circuit making capacity | 105 kA (Icm) at 220…440 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Icw] rated short-time withstand current | 50 kA (1 s) at 220…440 V AC 50/60 Hz conforming to IEC 60947-2 42 kA (1 s) at 690 V AC 50/60 Hz conforming to IEC 60947-2 25 kA (3 s) at 440/690 V AC 50/60 Hz conforming to IEC 60947-2 |
| Trip unit protection functions | LSIG |
| Protection type | Overload protection (long time) Short time short-circuit protection Earth fault Instantaneous short-circuit protection |
| Fault indication | Overload Internal fault Earth fault Short-circuit |
| Long time pick-up adjustment type Ir | Adjustable 9 settings |
| Long time pick-up adjustment range | 0.4…1 x In |
| Long time delay adjustment type | Adjustable 9 settings |
| [tr] long-time delay adjustment range | 0.5…24 s at 6 x Ir |
| Short-time pick-up adjustment type Isd | Adjustable 9 settings |
| [Isd] short-time pick-up adjustment range | 1.5…10 x Ir |
| Short-time delay adjustment type | Adjustable 5 settings |
| [tsd] short-time delay adjustment range | 100…400 ms |
| Instantaneous pick-up adjustment type Ii | Adjustable 9 settings |
| Instantaneous pick-up adjustment range | 2…15 x In Off |
| Ground-fault pick-up adjustment type | Adjustable 9 settings |
| Ground-fault time delay adjustment type -tg | Adjustable 5 settings |
| [tg] ground-fault time delay adjustment range | 100…400 ms |
| [Ig] ground-fault pick-up adjustment range | 500…1200 A |
| Zone selective interlocking ZSI | With |
| Current sensor rating range | 400/2000 A |
| Maximum breaking time | 25 ms |
| Maximum closing response time | 70 ms |
| Height | 439 mm |
| Width | 441 mm |
| Depth | 395 mm |
| Net weight | 70 kg |
| Environment | |
| Standards | IEC 60947-2 |
| Product certifications | CCC CCS IEC GOST |
| Pollution degree | 4 conforming to IEC 60664-1 |
| IP degree of protection | IP40 |
| Ambient air temperature for operation | -5…70 °C |
| Ambient air temperature for storage | -40…85 °C without control unit -25…85 °C with control unit |
| Packing Units | |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 43.9 cm |
| Package 1 Width | 44.1 cm |
| Package 1 Length | 49.5 cm |
| Package 1 Weight | 70 kg |
| Contractual warranty | |
| Warranty (in months) | 18 |
Customer Reviews
Related Products
XB5AR31N | Push button, Harmony XB5N XB7N, plastic, mushroom, green, 60mm, spring return, unmarked, 1 NO – Schneider Electric
SKU:
XB5AR31N
ZB2BW36C | Ø 22 mm fixing hole – push button head with blue lamp – Schneider Electric
SKU:
ZB2BW36C
MS13MD09 | 7MDL, 1HP 3 PHASE DOL STARTER – Schneider Electric
SKU:
MS13MD09
30002572 | EM1200 Energy meter Cl 0.5 RS485 LCD – Schneider Electric
SKU:
30002572