MX0 Mini Control contactor 4A 4P 415V AC 4NC AC-15 110V DC Coil L T CS940441OOO cs940441ooo mx0 04e dc front
MX0 Mini Control contactor 4A 4P 415V AC 4NC AC-15 24V DC Coil | L&T - CS940444OOO Original price was: ₹2,540.00.Current price is: ₹1,727.20. Excl. GST
Back to products
MX0 Mini Control contactor 4A 4P 415V AC 1NO 3NC AC-15 110V DC Coil L T CS940431OOO cs940431ooo mx0 13e dc front
MX0 Mini Control contactor 4A 4P 415V AC 1NO+3NC AC-15 220V DC Coil | L&T - CS940432OOO Original price was: ₹2,540.00.Current price is: ₹1,727.20. Excl. GST

MX0 Mini Control contactor 4A 4P 415V AC 1NO+3NC AC-15 110V DC Coil | L&T – CS940431OOO

SKU: CS940431OOO

Original price was: ₹2,540.00.Current price is: ₹1,727.20. Excl. GST

10 People watching this product now!

Order protection

Buy with complete confidence.

We back each order with genuine supply, on-time dispatch and GST or commercial invoicing as required.

Buyer protection on every order
Global DeliveryShipped pan-India and to export markets.
On-Time DeliveryPacked and dispatched on schedule.
100% OriginalFrom brand-authorised channels only.
GST InvoiceCompliant, ITC-ready tax invoice.
Secure PaymentEncrypted, trusted payment gateways.
Also included Dedicated account manager Technical support Bulk & business pricing 3-day replacement

Sourced through authorised channels, the CS940431OOO CS940431OOO contactor delivers dependable performance for motor control and switching. Key ratings include 4 A, 110V DC, 4 Poles. myelectric.in stocks the MX0 Mini Control contactor 4A 4P 415V AC 1NO+3NC AC-15 110V DC Coil | L&T for contractors, panel builders, and project buyers — buy online with GST invoice, or request a bulk quote for domestic supply and export to UAE, Singapore, UK, USA, Sri Lanka and more.

📋 Technical Specifications

ParameterValue
BrandCS940431OOO
Part Number / SKUCS940431OOO
CategoryContactor
Coil Voltage110V DC
Contact Configuration1 NO + 3 NC
Current Rating4 A
Poles4 Poles
Utilisation CategoryAC-3 (motor duty) / AC-1 (resistive)
Rated Frequency50/60 Hz
Motor Power (AC-3, 415V)Up to 4 kW
Coil Operating Range0.8–1.1 × rated coil voltage (Uc)
Mounting35mm DIN rail or screw fixing
StandardIEC 60947-4-1 / IS 13947-4-1
CertificationsBIS certified where applicable

⚡ Key Features

  • 4 A AC-3 rated — suits up to a 4 kW squirrel-cage induction motor at 415V for direct-on-line (DOL) starting and running.
  • 110V DC coil — connects directly to pushbutton station, PLC digital output, or timer relay; suitable for standard 50Hz Indian industrial control circuits.
  • 4 Poles main contacts with silver-alloy (AgSnO₂) tips — rated for AC-3 duty (DOL motor starting/stopping); low contact resistance reduces heat at rated current.
  • Manufactured to IEC 60947-4-1 / IS 13947-4-1 — complies with the applicable Indian BIS and IEC international standards for this product category.
  • BIS certified where applicable — meets Indian regulatory requirements for use in government, commercial, and industrial electrical installations.
  • Genuine authorised CS940431OOO product — sourced directly from the official distribution network with full manufacturer traceability and warranty.
  • GST invoice provided for India orders — valid for corporate procurement, government project orders, and public tender supply via myelectric.in.
  • Worldwide export available — UAE, Singapore, UK, USA, Sri Lanka & more. Contact +91 94814 00316 for bulk pricing and international shipping.

❓ Frequently Asked Questions

Q: Is the CS940431OOO rated 4 A for AC-3 motor duty or AC-1 resistive duty?

A: The 4 A rating of this CS940431OOO contactor applies to AC-3 duty (squirrel cage motor starting and running). For AC-1 (resistive/non-inductive) loads, the current can be up to ~1.3× the AC-3 rating. AC-4 (plugging/reversing) requires significant de-rating — consult the CS940431OOO selection table.

Q: The CS940431OOO has a coil voltage of 110V DC — what control supply is needed?

A: This CS940431OOO device requires a 110V DC control supply connected to the coil terminals (A1 and A2). For DC coils, observe polarity where marked. DC coils produce no inrush and are preferred for PLC output cards. Always fit a surge suppressor across the coil when switching with a PLC or solid-state relay.

Q: What is the electrical and mechanical life of the CS940431OOO?

A: CS940431OOO contactors are rated for millions of operations: typically 10–30 million mechanical operations and 1–3 million electrical operations at rated current and voltage (AC-3 duty). High-frequency switching applications (>10 operations/hour) require checking the specific thermal capacity of the contactor for continuous duty without overheating.

Q: Can the CS940431OOO be used for reversing duty (forward/reverse motor control)?

A: Contactors used for reversing must be wired with two contactors interlocked so only one can energise at a time. The CS940431OOO series provides mechanical interlock kits that physically prevent both contactors from closing simultaneously — mandatory for reversing and brake applications to prevent phase-to-phase short circuits.

Q: Can multiple CS940431OOO contactors be wired for star-delta starting?

A: Yes. Star-delta starters use three contactors: main (KM1), star (KM2), and delta (KM3). The CS940431OOO contactor series supports mechanical and electrical interlocking accessories that prevent simultaneous energisation of star and delta contactors — critical for safety. Ensure all three contactors are rated correctly for the motor FLC and star-delta transition current.