C10F3TM063 | Circuit breaker, ComPacT NSX100F, 36kA/415VAC, 3 poles, TMD trip unit 63A – Schneider Electric
₹25,440.00 Original price was: ₹25,440.00.₹12,720.00Current price is: ₹12,720.00. Excl. GST
Dispatch By : 2 Weeks
Dispatch By : 2 Weeks
Order protection
Buy with complete confidence.
We back each order with genuine supply, on-time dispatch and GST or commercial invoicing as required.
Additional Addons/Accessories
29450 | standard auxiliary contact, circuit breaker status OF-SD-SDE-SDV, 1 single contact – Schneider Electric
LV429454 | Wireless auxiliary contact NSX – Schneider Electric
LV429513 | TORQUE LIMITING SCREWS (SET OF 12) – Schneider Electric
LV429515 | 1 3P SHORT TERMINAL SHIELD – Schneider Electric
LV429337T | ROTARY HANDLE DIR 100-250 BLK – Schneider Electric
LV429388 | MX shunt trip release, Compact NSX, PowerPact Multistandard, EasyPact CVS, rated voltage 380 to 415 VAC 50/60 Hz, 440 to 480 VAC 60 Hz – Schneider Electric
LV429488 | Vigi 200-440V 3P for NSX100/160 – Schneider Electric
LV429354T | INTERLOCKING 100-250 FOR TOGGLE – Schneider Electric
LV429434 | motor mechanism, MT 100/160, Compact NSX100/160, PowerPact Multistandard H, 220 to 240 VAC 50/60 Hz, 208 to 277 VAC 60 Hz – Schneider Electric
LV429408 | MN 380-415V50/60HZ 440-480V60HZ UVR – Schneider Electric
LV429289 | COMPACT PLUG IN BASE KIT 3P – Schneider Electric
LV429387 | MX shunt trip release, Compact NSX, PowerPact Multistandard, EasyPact CVS, rated voltage 220 to 240 VAC 50/60 Hz, 208 to 277 VAC 60 Hz – Schneider Electric
LV429517 | 1 3P LONG TERMINAL SHIELD – Schneider Electric
LV429407 | MN undervoltage release, Compact NSX, PowerPact Multistandard, EasyPact CVS, rated voltage 220 to 240 VAC 50/60 Hz, 208 to 277 VAC 60 Hz – Schneider Electric
LV429329 | interphase barriers, Compact NSX 100/160/250, EasyPact CVS 100/160/250, set of 6 parts – Schneider Electric
LV429338T | ROTARY HANDLE EXT 100-250 BLK. – Schneider Electric
Looking for the C10F3TM063 | Circuit breaker, ComPacT NSX100F, 36kA/415VAC, 3 poles, TMD trip unit 63A? This genuine Schneider Electric mccb from the ComPacT range is built for reliable circuit protection and isolation, combining proven reliability with full compliance to applicable IEC/IS standards. Key ratings include 63 A at 40 °C, 690 V AC 50/60 Hz, 3P. Order part number C10F3TM063 from myelectric.in — a trusted Schneider Electric supplier offering competitive pricing, GST billing, and shipping across India and overseas.
📋 Technical Specifications
| Product | |
| Brand | Schneider Electric |
| Part Number / SKU | C10F3TM063 |
| Category | MCCB |
| Main | |
| Range | ComPacT |
| Product name | ComPacT NSX |
| Device short name | NSX100F |
| Product or component type | Circuit breaker |
| Device application | Distribution |
| Poles description | 3P |
| Protected poles description | 3D |
| [In] rated current | 63 A at 40 °C |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz |
| Network type | AC |
| Network frequency | 50/60 Hz |
| Suitability for isolation | Yes conforming to EN/IEC 60947-2 |
| Utilisation category | Category A |
| Breaking capacity | 85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 25 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 10 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1 |
| Breaking capacity code | F 36 kA 415 V AC |
| Trip unit name | TM-D |
| Trip unit technology | Thermal-magnetic |
| Trip unit protection functions | LI |
| Control type | Toggle |
| Circuit breaker mounting mode | Fixed |
| Complementary | |
| [Ui] rated insulation voltage | 800 V AC 50/60 Hz |
| [Uimp] rated impulse withstand voltage | 8 kV |
| [Ics] rated service breaking capacity | 85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 12 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 11 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 4 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 |
| Mechanical durability | 50000 cycles |
| Electrical durability | 50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In |
| Power dissipation per pole | 8.61 W |
| Mounting support | Backplate |
| Mounting position | Horizontal and vertical Flat on the back |
| Upside connection | Front |
| Downside connection | Front |
| Connection pitch | 35 mm |
| Protection type | L : for overload protection (thermal) I : for short-circuit protection (magnetic) |
| Trip unit rating | 63 A at 40 °C |
| Long-time pick-up adjustment type Ir (thermal protection) | Adjustable |
| [Ir] long-time protection pick-up adjustment range | 0.7…1 x In |
| Long-time protection delay adjustment type tr | Fixed |
| [tr] long-time delay adjustment range | 120…400 s at 1.5 x In 15 s at 6 x Ir |
| Instantaneous protection pick-up adjustment type Ii | Fixed |
| [Ii] instantaneous protection pick-up adjustment range | 500 A |
| Earth-leakage protection | Without |
| Number of slots | 5 slot(s) |
| Width (W) | 105 mm |
| Height (H) | 161 mm |
| Depth (D) | 86 mm |
| Product weight | 2.05 kg |
| Environment | |
| Standards | EN/IEC 60947-2 |
| Overvoltage category | III |
| Electrical shock protection class | Class II on front face |
| Pollution degree | 3 conforming to IEC 60664-1 |
| IP degree of protection | IP40 conforming to IEC 60529 |
| IK degree of protection | IK07 conforming to IEC 62262 |
| Ambient air temperature for operation | -25…70 °C |
| Ambient air temperature for storage | -50…85 °C |
| Relative humidity | 0…95 % |
| Operating altitude | 0…2000 m without derating 2000 m…5000 m with derating |
| Packing Units | |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 13.700 cm |
| Package 1 Width | 11.200 cm |
| Package 1 Length | 19.000 cm |
| Package 1 Weight | 1.778 kg |
| Unit Type of Package 2 | S03 |
| Number of Units in Package 2 | 7 |
| Package 2 Height | 30.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 12.848 kg |
| Contractual warranty | |
| Warranty (in months) | 18 |
⚡ Key Features
- 100 A frame rating — handles the full rated current continuously; designed for feeder and sub-distribution protection where fault levels exceed MCB capability.
- Performance level F — breaking capacity 36 kA (standard breaking capacity, suitable for commercial and light industrial boards).
- TMD (Thermal-Magnetic) trip unit — adjustable overload setting (Ir) from 0.7–1× In with fixed instantaneous magnetic trip; simple and reliable for standard feeder applications.
- 3 Poles — three-phase feeder protection; neutral not switched (TN-C / IT systems).
- CompacT NSX form factor — 70mm wide per pole; designed for high-density LV switchboards with up to 3 units per standard 250mm busbar bay.
- Rotary handle with padlocking points — LOTO compliant; handle locks in OFF position with up to 3 padlocks, preventing accidental energisation during maintenance.
- Manufactured to IEC 60947-2 / IS 13947-2 — complies with the applicable Indian BIS and IEC international standards for this product category.
- BIS certified, CE marked, RoHS compliant — meets Indian regulatory requirements for use in government, commercial, and industrial electrical installations.
- Genuine authorised Schneider Electric product — sourced directly from the official distribution network with full manufacturer traceability and warranty.
- GST invoice provided for India orders — valid for corporate procurement, government project orders, and public tender supply via myelectric.in.
🔗 Compatible Products & Accessories
The following genuine accessories and compatible devices are designed to work with this product. Contact myelectric.in for pricing and availability:
❓ Frequently Asked Questions
Q: What load can the C10F3TM063 protect at its rated 100 A?
A: The C10F3TM063 is rated to carry and protect circuits up to 100 A continuously. For motor loads, ensure the full-load current (FLC) of the motor does not exceed this rating. For resistive loads (heaters, lighting), the 100 A rating is used directly. Derate by 20% for ambient temperatures above 40°C.
Q: What does the 36 kA breaking capacity on the C10F3TM063 mean in practice?
A: Breaking capacity (36 kA) is the maximum prospective short-circuit current the C10F3TM063 can safely interrupt without damage. Before installing, verify that the prospective fault level at the installation point does not exceed 36 kA — this is checked using a fault level calculation or from the upstream transformer impedance data. Installing a breaker with insufficient breaking capacity is a serious safety violation.
Q: Can the C10F3TM063 be motorised for remote switching and automation?
A: Yes. Schneider Electric MCCBs in this series support rotary handle adaptation and motorised operating mechanisms as accessories, enabling remote ON/OFF switching via PLC, SCADA, or BMS. Motorised MCCBs are used for automatic load management and remote trip in automated distribution systems.
Q: What trip unit type does the C10F3TM063 use — thermal-magnetic or electronic?
A: The C10F3TM063 uses a thermal-magnetic TMD trip unit — thermal bimetal for overload protection and electromagnetic mechanism for short-circuit. Compact, reliable, and maintenance-free for standard applications.
Q: Is the C10F3TM063 suitable for use as a motor branch circuit protector (Type E coordination)?
A: MCCBs used for motor branch circuit protection must be coordinated with the downstream overload relay for Type 2 coordination (no damage to contactor or relay on short-circuit). Verify the Schneider Electric coordination table for the specific contactor-overload-MCCB combination to confirm Type 1 or Type 2 coordination is achieved.