LAEX3M7 TVS 3P LC1E40 65 COIL 220V AC 50 60Hz Schneider Electric laex3m7 image 1500x1500
LAEX3M7 | TVS 3P LC1E40~65 COIL 220V AC 50/60Hz - Schneider Electric Original price was: ₹7,280.00.Current price is: ₹4,222.40. Excl. GST
Back to products
LAEX5M5 EasyPact TVS coil 220 VAC 50 Hz spare part for LC1E120 E160 Schneider Electric laex5m5 image 1500x1500
LAEX5M5 | EasyPact TVS coil 220 VAC 50 Hz spare part for LC1E120...E160 - Schneider Electric Original price was: ₹10,120.00.Current price is: ₹5,869.60. Excl. GST

LAEX4M7 | COIL 220VAC 50/60HZ FOR 3P LC1E80…95 – Schneider Electric

SKU: LAEX4M7

Original price was: ₹9,090.00.Current price is: ₹5,272.20. Excl. GST

In stock

In stock

17 People watching this product now!

Order protection

Buy with complete confidence.

We back each order with genuine supply, on-time dispatch and GST or commercial invoicing as required.

Buyer protection on every order
Global DeliveryShipped pan-India and to export markets.
On-Time DeliveryPacked and dispatched on schedule.
100% OriginalFrom brand-authorised channels only.
GST InvoiceCompliant, ITC-ready tax invoice.
Secure PaymentEncrypted, trusted payment gateways.
Also included Dedicated account manager Technical support Bulk & business pricing 3-day replacement

Looking for the LAEX4M7 | COIL 220VAC 50/60HZ FOR 3P LC1E80…95? This genuine Schneider Electric contactor spare part from the Easy TeSys range is built for motor control and switching, combining proven reliability with full compliance to applicable IEC/IS standards. Key ratings include 220V AC, 3 Poles. Order part number LAEX4M7 from myelectric.in — a trusted Schneider Electric supplier offering competitive pricing, GST billing, and shipping across India and overseas.

📋 Technical Specifications

Product
BrandSchneider Electric
Part Number / SKULAEX4M7
CategoryContactor Spare Part
Main
RangeEasy TeSys
Range of productEasy TeSys Control
Product or component typeContactor coil
Device short nameLAEX
Packing Units
Unit Type of Package 1PCE
Number of Units in Package 11
Package 1 Height4.5 cm
Package 1 Width8.6 cm
Package 1 Length11.5 cm
Package 1 Weight0.183 kg
Contractual warranty
Warranty (in months)18

⚡ Key Features

  • Genuine Schneider Electric OEM accessory — manufactured to the same specification and tested to the same standards as the parent device; ensures mechanical and electrical compatibility that third-party alternatives cannot guarantee.
  • Replacement contactor coil rated 220V AC — restores the original contactor to service at a fraction of the cost of a complete replacement.
  • Exact-fit replacement — same electrical and mechanical specification as the factory-fitted coil; no recalibration or adjustment of the contactor required after fitting.
  • Direct clip-on or screw-mount to parent device — fits without panel modification or additional wiring between the accessory and main device; field-retrofittable.
  • Manufactured to IEC 60947 (tested as part of the parent device certification) — complies with the applicable Indian BIS and IEC international standards for this product category.
  • BIS certified, CE marked, RoHS compliant — meets Indian regulatory requirements for use in government, commercial, and industrial electrical installations.
  • Genuine authorised Schneider Electric product — sourced directly from the official distribution network with full manufacturer traceability and warranty.
  • GST invoice provided for India orders — valid for corporate procurement, government project orders, and public tender supply via myelectric.in.
  • Worldwide export available — UAE, Singapore, UK, USA, Sri Lanka & more. Contact +91 94814 00316 for bulk pricing and international shipping.

🔗 Compatible Products & Accessories

The following genuine accessories and compatible devices are designed to work with this product. Contact myelectric.in for pricing and availability:

LC1E80M7LC1E95M7

❓ Frequently Asked Questions

Q: The LAEX4M7 has a coil voltage of 220V AC — what control supply is needed?

A: This Schneider Electric device requires a 220V AC control supply connected to the coil terminals (A1 and A2). For AC coils, ensure the control circuit voltage is stable — voltage drops below 85% of rated coil voltage can cause chatter and coil overheating. Always fit a surge suppressor across the coil when switching with a PLC or solid-state relay.

Q: What causes a contactor coil to fail and need replacement like the LAEX4M7?

A: The most common causes are: sustained undervoltage (coil hums and overheats while failing to seal the magnetic circuit), overvoltage, voltage spikes from nearby switching inductive loads, dust or rust on the magnet faces preventing full closure (coil draws inrush current continuously), and simple ageing of the insulation. If coils fail repeatedly, fit a surge suppressor and check the control supply voltage stability before fitting the new coil.

Q: How do I know the LAEX4M7 replacement coil matches my contactor?

A: Match three things: (1) the contactor series and frame size stated for the LAEX4M7, (2) the coil voltage — the replacement must equal the control circuit voltage exactly, and (3) AC or DC supply type. Fitting a coil of the wrong voltage causes failure to pull in (too low) or coil burnout (too high). The original coil’s voltage is printed on its face — verify before ordering.