Looking for the GZ1LE10 | Motor circuit breaker,Easy TeSys Power,GZ1LE,3P,push-botton,6.3A,magnetic trip? This genuine Schneider Electric motor protection circuit breaker (mpcb) is built for reliable circuit protection and isolation, combining proven reliability with full compliance to applicable IEC/IS standards. Key ratings include 3 Poles. Order part number GZ1LE10 from myelectric.in — a trusted Schneider Electric supplier offering competitive pricing, GST billing, and shipping across India and overseas.
📋 Technical Specifications
| Parameter | Value |
|---|---|
| Brand | Schneider Electric |
| Part Number / SKU | GZ1LE10 |
| Category | Motor Protection Circuit Breaker (MPCB) |
| Poles | 3 Poles |
| Trip Class | Class 10A (per IEC 60947-4-1) |
| Rated Operational Voltage | Up to 690V AC |
| Rated Frequency | 50/60 Hz |
| Protection Functions | Thermal overload (adjustable), magnetic short-circuit, phase-loss |
| Mounting | 35mm DIN rail or screw fixing |
| Reset | Manual reset after trip |
| Standard | IEC 60947-4-1 and IEC 60947-2 |
| Certifications | BIS certified, CE marked, RoHS compliant |
⚡ Key Features
- Combined thermal and magnetic protection in one device — single MPCB replaces a separate motor-rated MCB plus thermal overload relay, saving DIN rail space and inter-device wiring.
- Phase-loss and phase-unbalance detection — trips within seconds of a phase failure, protecting the motor from the severe overheating that single-phasing causes within minutes.
- Manual reset only — operator must acknowledge and reset the MPCB after a trip, preventing automatic restart that could damage the motor or driven machinery.
- Manufactured to IEC 60947-4-1 and IEC 60947-2 — complies with the applicable Indian BIS and IEC international standards for this product category.
- BIS certified, CE marked, RoHS compliant — meets Indian regulatory requirements for use in government, commercial, and industrial electrical installations.
- Genuine authorised Schneider Electric product — sourced directly from the official distribution network with full manufacturer traceability and warranty.
- GST invoice provided for India orders — valid for corporate procurement, government project orders, and public tender supply via myelectric.in.
- Worldwide export available — UAE, Singapore, UK, USA, Sri Lanka & more. Contact +91 94814 00316 for bulk pricing and international shipping.
❓ Frequently Asked Questions
Q: What is the trip class of the GZ1LE10 and what motor starting time does it allow?
A: MPCBs are typically rated Class 10 (trips in ≤10 seconds at 7.2× setting current), suitable for normal motors with DOL starting times up to 10 seconds. Heavy-duty motors (large fans, centrifuges, compressors) with longer starting times may need Class 20 or Class 30 protection — check the starting time against the motor’s speed-torque curve and select accordingly.
Q: Can the GZ1LE10 replace a contactor + overload relay combination in a motor circuit?
A: The GZ1LE10 provides motor short-circuit protection and overload protection in one device — but it cannot make/break motor current under normal operational switching (that is the contactor’s role). For motor starters requiring on/off switching, the GZ1LE10 is used as the upstream protection device with a contactor for switching. Some MPCB series include a direct handle for manual starting of small motors without a separate contactor.
Q: Which Schneider Electric accessories are compatible with the GZ1LE10?
A: The Schneider Electric GZ1LE10 series supports snap-on accessories including auxiliary contacts (OF), alarm contacts (SD), shunt trip coils (MX), undervoltage releases (MN), and comb busbars. Accessories are series-specific — always verify compatibility using the Schneider Electric product catalogue before ordering. myelectric.in can advise on the correct accessory part numbers for the GZ1LE10.
Q: What is the difference between a Motor Protection Circuit Breaker (MPCB) and a standard MCB — and why use the GZ1LE10?
A: A standard MCB protects against overload and short-circuit only. A Motor Protection Circuit Breaker (MPCB) adds adjustable thermal overload matched to motor FLC, Class 10/20 trip curves for motor starting inrush, and phase-loss sensitivity — making it the correct device for motor branch circuits where a standard MCB would either nuisance-trip on motor starting or fail to protect adequately against slow overloads. Choose the GZ1LE10 when the application specifically requires motor protection circuit breaker (mpcb) characteristics.