The Schneider Electric A9N26613 is an earth leakage add-on block (vigi) from the Acti9 range, engineered for industrial, commercial, and infrastructure applications in demanding Indian and international installations. Key ratings include 63 A, 230…240 V AC 50/60 Hz, 2P. Buy the A9N26613 | VIGI XC60- earth leakage add-on block 2P 63A AC 300MA online at myelectric.in with GST invoice, genuine-product assurance, and fast delivery across India — bulk and worldwide export enquiries welcome.
📋 Technical Specifications
| Product | |
| Brand | Schneider Electric |
| Part Number / SKU | A9N26613 |
| Category | Earth Leakage Add-on Block (Vigi) |
| Main | |
| Range | Acti9 |
| Product or component type | Add-on residual current device |
| Device short name | Vigi xC60 |
| Poles description | 2P |
| [In] rated current | 63 A |
| Earth-leakage sensitivity | 300 mA |
| Earth-leakage protection time delay | Instantaneous |
| Earth leakage protection type | Type AC |
| Network type | AC |
| Network frequency | 50/60 Hz |
| [Ue] rated operational voltage | 230…240 V AC 50/60 Hz conforming to EN/IEC 61009-1 230…240 V conforming to EN/IEC 61009-2-1 |
| Standards | EN/IEC 61009-2-1 EN/IEC 61009-1 |
| 9 mm pitches | 4 |
| Complementary | |
| Device location in system | Outgoer |
| Residual current tripping technology | Voltage independent Electromechanical |
| [Ui] rated insulation voltage | 500 V AC 50/60 Hz |
| [Uimp] rated impulse withstand voltage | 6 kV |
| Range compatibility | Acti9 iC60 |
| Local signalling | Red indicator light on the front face |
| Mounting mode | Clip-on |
| Mounting support | DIN rail |
| Electrical connection to mcb | By screws |
| Height | 87 mm |
| Width | 72 mm |
| Depth | 74.5 mm |
| Product weight | 150 g |
| Connections – terminals | Tunnel type terminal downside for 1 cable(s) 1…35 mm² rigid without cable end Tunnel type terminal downside for 1 cable(s) 1…25 mm² flexible without cable end Tunnel type terminal downside for 1 cable(s) 1…25 mm² flexible with cable end |
| Wire stripping length | 14 mm for bottom connection |
| Tightening torque | 3.5 N.m bottom |
| Environment | |
| IP degree of protection | IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529 |
| Pollution degree | 3 |
| Electromagnetic compatibility | 8/20 µs impulse withstand, 250 A |
| Ambient air temperature for operation | -5…60 °C |
| Ambient air temperature for storage | -40…85 °C |
| Packing Units | |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 7.5 cm |
| Package 1 Width | 8.5 cm |
| Package 1 Length | 11.5 cm |
| Package 1 Weight | 0.166 kg |
| Unit Type of Package 2 | S03 |
| Number of Units in Package 2 | 27 |
| Package 2 Height | 30.0 cm |
| Package 2 Width | 30.0 cm |
| Package 2 Length | 40.0 cm |
| Package 2 Weight | 4.969 kg |
| Contractual warranty | |
| Warranty (in months) | 18 |
⚡ Key Features
- 63 A current rating — confirmed from product specifications; size wiring and terminals to match or exceed this value.
- Manufactured to IS/IEC 60947, IS 8828 (MCBs), IS 13947, IEC 61439 (DBs) — complies with Indian BIS and IEC international safety standards.
- BIS certified, CE marked, RoHS compliant — meets Indian regulatory requirements for use in government, commercial, and industrial electrical installations.
- Genuine authorised Schneider Electric product — sourced directly from the official distribution network with full manufacturer traceability and warranty.
- GST invoice provided for India orders — valid for corporate procurement, government project orders, and public tender supply via myelectric.in.
- Worldwide export available — UAE, Singapore, UK, USA, Sri Lanka & more. Contact +91 94814 00316 for bulk pricing and international shipping.
❓ Frequently Asked Questions
Q: What is the significance of the 63 A rating on the A9N26613?
A: The 63 A rating is the device’s maximum continuous current carrying capacity under specified conditions (typically 40°C ambient). For circuit design, use 80% of this value as the design current to allow for derating due to grouping, temperature, and future load growth.
Q: Why is the 300 mA sensitivity specified on the A9N26613 and when should you choose a different rating?
A: 300 mA is the residual current at which the A9N26613 will trip within 300ms. A 30mA sensitivity provides additional shock protection (mandatory for socket circuits per IS 732). 100mA is used for fire protection (no shock protection). 300mA protects feeders without nuisance tripping. Choose based on the circuit’s risk profile — never use >30mA for socket outlet circuits in wet or high-risk locations.