TPRSM001 | TeSys island SIL Interface - Schneider Electric
TPRSM001 | TeSys island SIL Interface - Schneider Electric Original price was: ₹13,905.00.Current price is: ₹7,786.80. Excl. GST
Back to products
TPRSS025 | TeSys island SIL Starter 25 A / 7,5 kW - Schneider Electric
TPRSS025 | TeSys island SIL Starter 25 A / 7,5 kW - Schneider Electric Original price was: ₹28,965.00.Current price is: ₹16,220.40. Excl. GST

TPRSS009 | TeSys island SIL Starter 9 A / 4 kW – Schneider Electric

SKU: TPRSS009

Original price was: ₹15,000.00.Current price is: ₹8,400.00. Excl. GST

Dispatch By : 2 Weeks

Dispatch By : 2 Weeks

16 People watching this product now!

Order protection

Buy with complete confidence.

We back each order with genuine supply, on-time dispatch and GST or commercial invoicing as required.

Buyer protection on every order
Global DeliveryShipped pan-India and to export markets.
On-Time DeliveryPacked and dispatched on schedule.
100% OriginalFrom brand-authorised channels only.
GST InvoiceCompliant, ITC-ready tax invoice.
Secure PaymentEncrypted, trusted payment gateways.
Also included Dedicated account manager Technical support Bulk & business pricing 3-day replacement

Specifications

Main
RangeTeSys
Product nameTeSys island
Device short nameTPRSS
Product or component typeSIL motor starter
Motor starter typeDirect on line
Device presentationDirect starter connected to an automation controller through a bus coupler
Operational only when connected to a bus coupler
Function availableUpstream voltage presence detection
Electrical line and load protection
Power and energy monitoring when connected with TPRVM voltage module
Safe stop function available when connected with a TPRSM module
Product compatibilityTPRBC bus coupler
TPRVM voltage interface module
TPRSM SIL interface module
Poles description3P (3 NO)
Utilisation categoryAC-1
AC-2
AC-3
AC-4
AC-3e
Motor power kW2.2 kW at 230 V 50 Hz (AC-3)
4 kW at 380…415 V 50 Hz (AC-3)
4 kW at 440 V 50 Hz (AC-3)
5.5 kW at 500 V 50 Hz (AC-3)
5.5 kW at 690 V 50 Hz (AC-3)
motor power HP (UL / CSA)0.33 hp at 120 V AC 60 Hz for 1 phase motors
1 hp at 240 V AC 60 Hz for 1 phase motors
2 hp at 208 V AC 60 Hz for 3 phases motors
2 hp at 240 V AC 60 Hz for 3 phases motors
5 hp at 480 V AC 60 Hz for 3 phases motors
7.5 hp at 600 V AC 60 Hz for 3 phases motors
[Ue] rated operational voltage<= 690 V AC 47…63 Hz
[Ie] rated operational current9 A (at <50 °C) at <= 440 V AC-3
15 A (at <50 °C) at <= 440 V AC-1
[Ith] conventional free air thermal current15 A (at 50 °C)
[Ui] rated insulation voltage690 V conforming to IEC 60947-4-1
600 V conforming to UL 60947-4-1
600 V conforming to CSA C22.2 No 60947-4-1
[Uimp] rated impulse withstand voltage6 kV conforming to IEC 60947-1
Overvoltage categoryIII
Thermal protection adjustment range0.18…9 A
Thermal overload classClass 5…30
ResetRemotely or automatically
Irms rated making capacity250 A at 440 V conforming to IEC 60947
Rated breaking capacity250 A at 440 V conforming to IEC 60947
[Icw] rated short-time withstand current210 A 40 °C – 1 s
105 A 40 °C – 10 s
61 A 40 °C – 1 min
30 A 40 °C – 10 min
Average impedance2.5 mOhm – Ith 15 A 50 Hz
Power dissipation per pole0.2 W AC-3 – Ith 9 A
0.56 W AC-1 – Ith 15 A
[Uc] control circuit voltage24 V DC supplied by the bus coupler
Current consumption160 mA contactor sealed
160 mA contactor closing
Power dissipation in W3.5 W at Ie AC-3
Complementary
Mechanical durability30 Mcycles
Electrical durability2 Mcycles 9 A AC-3 at Ue 440 V
1.2 Mcycles 15 A AC-1 at Ue 440 V
Maximum operating rate3600 cyc/mn AC-3
Operating time< 100 ms closing
< 30 ms opening
Safety functionSafe stop: category 0 conforming to IEC 60204-1 when associated with a TPRSM module
Safe stop: category 1 conforming to IEC 60204-1 when associated with a TPRSM module
Safety integrity levelSIL 2 conforming to IEC 61508 in single channel system architecture
SILCL 2 conforming to IEC 62061 in single channel system architecture
PL = d category 2 conforming to ISO 13849-1 in single channel system architecture
Safety performance levelB10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Protection typeThermal overload protection
Motor overheat
Overcurrent
Undercurrent
Jam
Long start
Stall
Rapid cycle lockout
Rapid restart lockout
Phase sequence
Phase loss
Phase reversal
Phase unbalance
Ground current
Monitoring typeTime device ON
Time device switch ON
Number of faults
Number of switching cycles
Number of device power cycles
Average current Iavg
Average voltage Vavg
Max current Imax
Max voltage Vmax
Active and reactive power with voltage module
Active and reactive energy with voltage module
True power factor with voltage module
Local signalling1 LED (green/red) for DS (device status)
1 LED (green/red) for LS (load status)
StandardsEN/IEC 60947-1
EN/IEC 60947-4-1
UL 60947-4-1
CSA C22.2 No 60947-4-1
Product certificationsEAC
UL
CSA
CCC
Mounting modeHorizontal and vertical (35 mm symmetrical DIN rail)
Connections – terminalsScrew-clamp terminals 1 cable(s) 1…4 mm² (16 AWG…12 AWG) rigid
Screw-clamp terminals 2 cable(s) 1…4 mm² (16 AWG…12 AWG) rigid
Screw-clamp terminals 1 cable(s) 1.5…4 mm² (16 AWG…12 AWG) flexible without cable end
Screw-clamp terminals 2 cable(s) 1.5…4 mm² (16 AWG…12 AWG) flexible without cable end
Screw-clamp terminals 1 cable(s) 1…4 mm² (16 AWG…12 AWG) flexible with cable end
Screw-clamp terminals 2 cable(s) 1…2.5 mm² (16 AWG…14 AWG) flexible with cable end
Tightening torque1.7 N.m – with screwdriver flat Ø 6 mm
1.7 N.m – with screwdriver Philips No 2
Width45 mm
Height116 mm
Depth115 mm
Net weight0.656 kg
Environment
Ambient air temperature for storage-25…70 °C
Ambient air temperature for operation-10…50 °C without derating
50…60 °C with current derating
Relative humidity5…95 %
Operating altitude0…2000 m without derating
IP degree of protectionIP20
Pollution degree2
Protective treatmentTC
Fire resistance960 °C conforming to UL 94
850 °C conforming to IEC 60695-2-1
650 °C conforming to IEC 60695-2-12
Shock resistance15 gn (duration = 11 ms) conforming to IEC 60068-2-27
Vibration resistance1.5 mm peak to peak (f= 3…13 Hz) conforming to IEC 60068-2-6
1 gn (f= 13…200 Hz) conforming to IEC 60068-2-6
Electromagnetic compatibilityElectrostatic discharge immunity test, level 3, 8 kV air, 6 kV contact, conforming to EN/IEC 61000-4-2
Radiated RF field immunity test, level 3, 10 V/m, conforming to EN/IEC 61000-4-3
Fast transient immunity test, level 4, 4 kV, conforming to EN/IEC 61000-4-4
Surge immunity test (differential mode), level 3, 2 kV, conforming to EN/IEC 61000-4-5
Surge immunity test (common mode), level 4, 4 kV, conforming to EN/IEC 61000-4-5
Conducted RF disturbance immunity test, 20 V, conforming to EN/IEC 61000-4-6
Packing Units
Unit Type of Package 1PCE
Number of Units in Package 11
Package 1 Height5.000 cm
Package 1 Width12.500 cm
Package 1 Length13.000 cm
Package 1 Weight712.000 g
Unit Type of Package 2S02
Number of Units in Package 214
Package 2 Height15.000 cm
Package 2 Width30.000 cm
Package 2 Length40.000 cm
Package 2 Weight10.252 kg
Contractual warranty
Warranty (in months)18

Customer Reviews