LXD1B7 | TeSys D – contactor coil – LXD1 – 24 V AC 50/60 Hz for 9… 38 A contactor – Schneider Electric
₹2,390.00 Original price was: ₹2,390.00.₹1,314.50Current price is: ₹1,314.50. Excl. GST
Dispatch By : 2 Weeks
Dispatch By : 2 Weeks
Order protection
Buy with complete confidence.
We back each order with genuine supply, on-time dispatch and GST or commercial invoicing as required.
Additional Addons/Accessories
LC1DT20B7 | TeSys 4P CONTACTOR 20A AC-1 230VAC COIL – Schneider Electric
LC1D09B7 | TeSys D contactor – 3P(3 NO) – AC-3 – <= 440 V 9 A - 24 V AC coil - Schneider Electric
CAD32B7 | TeSys D control relay – 3 NO + 2 NC – <= 690 V - 24 V AC standard coil - Schneider Electric
LC1DT25B7 | TeSys 4P CONTACTOR 25A AC-1 24VAC COIL – Schneider Electric
LC1D25B7 | TeSys D contactor – 3P(3 NO) – AC-3 – <= 440 V 25 A - 24 V AC coil - Schneider Electric
LC1D18B7 | TeSys D contactor – 3P(3 NO) – AC-3 – <= 440 V 18 A - 24 V AC coil - Schneider Electric
LC1D38B7 | TeSys CTR 38 AC3 18.5KW 1NO1NC24VAC COIL – Schneider Electric
LC1D128B7 | TeSys D contactor – 4P(2 NO + 2 NC) – AC-1 – <= 440 V 25 A - 24 V AC coil - Schneider Electric
LC1D12B7 | TeSys D contactor – 3P(3 NO) – AC-3 – <= 440 V 12 A - 24 V AC coil - Schneider Electric
LC1DT32B7 | TeSys 4P CONTACTOR 32A AC-1 24VAC COIL – Schneider Electric
LC1D32B7 | TeSys D contactor – 3P(3 NO) – AC-3 – <= 440 V 32 A - 24 V AC coil - Schneider Electric
LC1D098B7 | TeSys 4P CTR 20A AC-1 2NO 2NC 24VAC COIL – Schneider Electric
Looking for the LXD1B7 | TeSys D – contactor coil – LXD1 – 24 V AC 50/60 Hz for 9… 38 A contactor? This genuine Schneider Electric contactor spare part from the TeSys range is built for motor control and switching, combining proven reliability with full compliance to applicable IEC/IS standards. Key ratings include 38 A, 24V AC. Order part number LXD1B7 from myelectric.in — a trusted Schneider Electric supplier offering competitive pricing, GST billing, and shipping across India and overseas.
📋 Technical Specifications
| Product | |
| Brand | Schneider Electric |
| Part Number / SKU | LXD1B7 |
| Category | Contactor Spare Part |
| Main | |
| Range | TeSys |
| Product or component type | Contactor coil |
| Device short name | LXD1 |
| Control circuit type | AC at 50/60 Hz |
| [Uc] control circuit voltage | 24 V AC 50/60 Hz |
| Average resistance | 5.37 Ohm at 20 °C |
| Inductance of closed circuit | 0.22 H |
| Product compatibility | LC1D09…D38 CAD LC1DT20…DT40 |
| Mechanical durability | 15 Mcycles |
| Maximum operating rate | 3600 cyc/h 60 °C |
| Complementary | |
| Coil technology | Without built-in suppressor module |
| Control circuit voltage limits | Drop-out: 0.3…0.6 Uc at 50/60 Hz (at <60 °C) Operational: 0.8…1.1 Uc at 50 Hz (at <60 °C) Operational: 0.85…1.1 Uc at 60 Hz (at <60 °C) |
| Inrush power in VA | 70 VA 60 Hz cos phi 0.75 (at 20 °C) 70 VA 50 Hz cos phi 0.75 (at 20 °C) |
| Hold-in power consumption in VA | 7.5 VA 60 Hz cos phi 0.3 (at 20 °C) 7 VA 50 Hz cos phi 0.3 (at 20 °C) |
| Heat dissipation | 2…3 W at 50/60 Hz |
| Environment | |
| Ambient air temperature for operation | -5…60 °C |
| Product weight | 0.07 kg |
| Packing Units | |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 4.500 cm |
| Package 1 Width | 6.300 cm |
| Package 1 Length | 4.000 cm |
| Package 1 Weight | 66.000 g |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 100 |
| Package 2 Height | 15.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 7.744 kg |
| Contractual warranty | |
| Warranty (in months) | 18 |
⚡ Key Features
- Genuine Schneider Electric OEM accessory — manufactured to the same specification and tested to the same standards as the parent device; ensures mechanical and electrical compatibility that third-party alternatives cannot guarantee.
- Replacement contactor coil rated 24V AC — restores the original contactor to service at a fraction of the cost of a complete replacement.
- Exact-fit replacement — same electrical and mechanical specification as the factory-fitted coil; no recalibration or adjustment of the contactor required after fitting.
- Direct clip-on or screw-mount to parent device — fits without panel modification or additional wiring between the accessory and main device; field-retrofittable.
- Manufactured to IEC 60947 (tested as part of the parent device certification) — complies with the applicable Indian BIS and IEC international standards for this product category.
- BIS certified, CE marked, RoHS compliant — meets Indian regulatory requirements for use in government, commercial, and industrial electrical installations.
- Genuine authorised Schneider Electric product — sourced directly from the official distribution network with full manufacturer traceability and warranty.
- GST invoice provided for India orders — valid for corporate procurement, government project orders, and public tender supply via myelectric.in.
- Worldwide export available — UAE, Singapore, UK, USA, Sri Lanka & more. Contact +91 94814 00316 for bulk pricing and international shipping.
🔗 Compatible Products & Accessories
The following genuine accessories and compatible devices are designed to work with this product. Contact myelectric.in for pricing and availability:
❓ Frequently Asked Questions
Q: Is the LXD1B7 rated 38 A for AC-3 motor duty or AC-1 resistive duty?
A: The 38 A rating of this Schneider Electric contactor applies to AC-3 duty (squirrel cage motor starting and running). For AC-1 (resistive/non-inductive) loads, the current can be up to ~1.3× the AC-3 rating. AC-4 (plugging/reversing) requires significant de-rating — consult the Schneider Electric selection table.
Q: The LXD1B7 has a coil voltage of 24V AC — what control supply is needed?
A: This Schneider Electric device requires a 24V AC control supply connected to the coil terminals (A1 and A2). For AC coils, ensure the control circuit voltage is stable — voltage drops below 85% of rated coil voltage can cause chatter and coil overheating. Always fit a surge suppressor across the coil when switching with a PLC or solid-state relay.
Q: What causes a contactor coil to fail and need replacement like the LXD1B7?
A: The most common causes are: sustained undervoltage (coil hums and overheats while failing to seal the magnetic circuit), overvoltage, voltage spikes from nearby switching inductive loads, dust or rust on the magnet faces preventing full closure (coil draws inrush current continuously), and simple ageing of the insulation. If coils fail repeatedly, fit a surge suppressor and check the control supply voltage stability before fitting the new coil.
Q: How do I know the LXD1B7 replacement coil matches my contactor?
A: Match three things: (1) the contactor series and frame size stated for the LXD1B7, (2) the coil voltage — the replacement must equal the control circuit voltage exactly, and (3) AC or DC supply type. Fitting a coil of the wrong voltage causes failure to pull in (too low) or coil burnout (too high). The original coil’s voltage is printed on its face — verify before ordering.