LC1D95U7 | 3P CONT 95A AC3 45KW 1NO 1NC 240VAC COIL – Schneider Electric
₹45,660.00 Original price was: ₹45,660.00.₹20,547.00Current price is: ₹20,547.00. Excl. GST
Dispatch By : 3 Weeks
Dispatch By : 3 Weeks
Order protection
Buy with complete confidence.
We back each order with genuine supply, on-time dispatch and GST or commercial invoicing as required.
Additional Addons/Accessories
LA4DFB | INTERFACE MODULE RELAY 24VDC – Schneider Electric
LADN13 | Auxiliary contact block, TeSys D, 1NO + 3NC, front mounting, screw clamp terminals – Schneider Electric
LA4DT2U | ELECTRONIC TIMER DELAY ON 1.5 – 30SEC – Schneider Electric
LADR0 | TeSys D – time delay auxiliary contact block – 1 NO + 1 NC screw clamp terminals – Schneider Electric
LADN04 | Auxiliary contact block, TeSys D, 4NC, front mounting, screw clamp terminals – Schneider Electric
LA9D80962 | CONNECTIONS 3P D80/D95 – Schneider Electric
LADN22 | Auxiliary contact block, TeSys D, 2NO + 2NC, front mounting, screw clamp terminals – Schneider Electric
LAD8N11 | Auxiliary contact block, TeSys D, 1NO + 1NC, side mounting, screw clamp terminals – Schneider Electric
LADT4 | TeSys D – time delay auxiliary contact block – 1 NO + 1 NC screw clamp terminals – Schneider Electric
LADT2 | TeSys D – time delay auxiliary contact block – 1 NO + 1 NC screw clamp terminals – Schneider Electric
LADS2 | TeSys D – time delay auxiliary contact block – 1 NO + 1 NC screw clamp terminals – Schneider Electric
LA9D4002 | Mechanical and electrical interlock, TeSys D reversing & changeover, 2 contactors LC1D80-D95 AC coil – Schneider Electric
LADN40 | Auxiliary contact block, TeSys D, 4NO, front mounting, screw clamp terminals – Schneider Electric
LADN22S | TeSys AUXILIARY CONTACT BLOCK 2NO-2NC – Schneider Electric
LA4DT4U | ELECTRONIC TIMER DELAY ON 25- 500 SEC – Schneider Electric
LA4DT0U | ELECTRONIC TIMER DELAY ON 0.1 – 2SEC – Schneider Electric
LA9D8069 | REVERS KIT FOR D80-95 – Schneider Electric
LAD8N20 | Auxiliary contact block, TeSys D, 2NO, side mounting, screw clamp terminals – Schneider Electric
LAD9ET3S | Safety Cover Red for TeSys Deca 80-95A – Schneider Electric
LADN20 | Auxiliary contact block, TeSys D, 2NO, front mounting, screw clamp terminals – Schneider Electric
LADR4 | TeSys D – time delay auxiliary contact block – 1 NO + 1 NC screw clamp terminals – Schneider Electric
LADN31 | Auxiliary contact block, TeSys D, 3NO + 1NC, front mounting, screw clamp terminals – Schneider Electric
LAD8N02 | Auxiliary contact block, TeSys D, 2NC, side mounting, screw clamp terminals – Schneider Electric
LADR2 | TeSys D – time delay auxiliary contact block – 1 NO + 1 NC screw clamp terminals – Schneider Electric
LA4DA2U | TeSys D – suppressor module – RC circuit – 110…240 V AC – Schneider Electric
LA4DWB | DC SUPPLY BLOCK – Schneider Electric
LA9D50978 | INTERLOK FOR CONTACTOR – Schneider Electric
LADN11 | Auxiliary contact block, TeSys D, 1NO + 1NC, front mounting, screw clamp terminals – Schneider Electric
LA4DE2U | VARISTOR SUPPRES 110-250VAC FOR D80-D115 – Schneider Electric
LADN02 | Auxiliary contact block, TeSys D, 2NC, front mounting, screw clamp terminals – Schneider Electric
LADT0 | TeSys D – time delay auxiliary contact block – 1 NO + 1 NC screw clamp terminals – Schneider Electric
Looking for the LC1D95U7 | 3P CONT 95A AC3 45KW 1NO 1NC 240VAC COIL? This genuine Schneider Electric electrical component from the TeSys range is built for industrial, commercial, and infrastructure applications, combining proven reliability with full compliance to applicable IEC/IS standards. Key ratings include 95 A, Power circuit: <= 690 V AC 25...400 Hz, 3P. Order part number LC1D95U7 from myelectric.in — a trusted Schneider Electric supplier offering competitive pricing, GST billing, and shipping across India and overseas.
📋 Technical Specifications
| Product | |
| Brand | Schneider Electric |
| Part Number / SKU | LC1D95U7 |
| Category | Electrical Component |
| Main | |
| Range | TeSys |
| Range of product | TeSys Deca |
| Product or component type | Contactor |
| Device short name | LC1D |
| Contactor application | Motor control Resistive load |
| Utilisation category | AC-3 AC-3e AC-4 AC-1 |
| Poles description | 3P |
| [Ue] rated operational voltage | Power circuit: <= 690 V AC 25…400 Hz |
| [Ie] rated operational current | 95 A (at <60 °C) at <= 440 V AC-3 for power circuit 125 A (at <60 °C) at <= 1000 V AC-1 for power circuit 95 A (at <60 °C) at <= 440 V AC-3e for power circuit |
| [Uc] control circuit voltage | 240 V AC 50/60 Hz |
| Complementary | |
| Motor power kW | 25 kW at 220…230 V AC 50 Hz (AC-3) 45 kW at 380…400 V AC 50 Hz (AC-3) 45 kW at 415…440 V AC 50 Hz (AC-3) 55 kW at 500 V AC 50 Hz (AC-3) 45 kW at 660…690 V AC 50 Hz (AC-3) 15 kW at 400 V AC 50 Hz (AC-4) 25 kW at 220…230 V AC 50 Hz (AC-3e) 45 kW at 380…400 V AC 50 Hz (AC-3e) 45 kW at 415…440 V AC 50 Hz (AC-3e) 55 kW at 500 V AC 50 Hz (AC-3e) 45 kW at 660…690 V AC 50 Hz (AC-3e) |
| Motor power hp | 7.5 hp at 120 V AC 60 Hz for 1 phase motors 15 hp at 230/240 V AC 60 Hz for 1 phase motors 30 hp at 200/208 V AC 60 Hz for 3 phases motors 30 hp at 230/240 V AC 60 Hz for 3 phases motors 60 hp at 460/480 V AC 60 Hz for 3 phases motors 60 hp at 575/600 V AC 60 Hz for 3 phases motors |
| Compatibility code | LC1D |
| Pole contact composition | 3 NO |
| Protective cover | With |
| [Ith] conventional free air thermal current | 10 A (at 60 °C) for signalling circuit 125 A (at 60 °C) for power circuit |
| Irms rated making capacity | 1100 A at 440 V AC for power circuit conforming to IEC 60947 140 A AC for signalling circuit conforming to IEC 60947-5-1 250 A DC for signalling circuit conforming to IEC 60947-5-1 |
| Rated breaking capacity | 1100 A at 440 V for power circuit conforming to IEC 60947 |
| [Icw] rated short-time withstand current | 1100 A 40 °C – 1 s for power circuit 800 A 40 °C – 10 s for power circuit 400 A 40 °C – 1 min for power circuit 135 A 40 °C – 10 min for power circuit 140 A – 100 ms for signalling circuit 120 A – 500 ms for signalling circuit 100 A – 1 s for signalling circuit |
| Associated fuse rating | 10 A gG for signalling circuit conforming to IEC 60947-5-1 200 A gG at <= 690 V coordination type 1 for power circuit 160 A gG at <= 690 V coordination type 2 for power circuit |
| Average impedance | 0.8 mOhm – Ith 125 A 50 Hz for power circuit |
| Power dissipation per pole | 12.5 W AC-1 7.2 W AC-3 7.2 W AC-3e |
| [Ui] rated insulation voltage | Power circuit: 1000 V conforming to IEC 60947-4-1 Power circuit: 600 V CSA certified Power circuit: 600 V UL certified Signalling circuit: 690 V conforming to IEC 60947-1 Signalling circuit: 600 V CSA certified Signalling circuit: 600 V UL certified |
| Overvoltage category | III |
| Pollution degree | 3 |
| [Uimp] rated impulse withstand voltage | 8 kV conforming to IEC 60947 |
| Safety reliability level | B10d = 1.3 Mcycles contactor with nominal load conforming to EN/ISO 13849-1 B10d = 20 Mcycles contactor with mechanical load conforming to EN/ISO 13849-1 |
| Mechanical durability | 4 Mcycles |
| Electrical durability | 1.2 Mcycles 95 A AC-3 1.3 Mcycles 125 A AC-1 1.2 Mcycles 95 A AC-3e |
| Control circuit type | AC at 50/60 Hz |
| Coil technology | Without built-in suppressor module |
| Control circuit voltage limits | 0.8…1.1 Uc (-40…55 °C):operational AC 50 Hz 0.85…1.1 Uc (-40…55 °C):operational AC 60 Hz 0.3…0.6 Uc (-40…70 °C):drop-out AC 50/60 Hz 1…1.1 Uc (55…70 °C):operational AC 50/60 Hz |
| Inrush power in VA | 245 VA 60 Hz cos phi 0.75 (at 20 °C) 245 VA 50 Hz cos phi 0.75 (at 20 °C) |
| Hold-in power consumption in VA | 26 VA 60 Hz cos phi 0.3 (at 20 °C) 26 VA 50 Hz cos phi 0.3 (at 20 °C) |
| Heat dissipation | 6…10 W at 50/60 Hz |
| Operating time | 20…35 ms closing 6…20 ms opening |
| Maximum operating rate | 3600 cyc/h at 60 °C |
| Connections – terminals | Control circuit: screw clamp terminals 2 1…2.5 mm² – cable stiffness: flexible with cable end Control circuit: screw clamp terminals 1 1…2.5 mm² – cable stiffness: flexible with cable end Control circuit: screw clamp terminals 1 1…4 mm² – cable stiffness: flexible without cable end Control circuit: screw clamp terminals 2 1…4 mm² – cable stiffness: flexible without cable end Control circuit: screw clamp terminals 1 1…4 mm² – cable stiffness: solid without cable end Control circuit: screw clamp terminals 2 1…4 mm² – cable stiffness: solid without cable end Power circuit: connector 1 4…50 mm² – cable stiffness: flexible without cable end Power circuit: connector 2 4…25 mm² – cable stiffness: flexible without cable end Power circuit: connector 1 4…50 mm² – cable stiffness: flexible with cable end Power circuit: connector 2 4…16 mm² – cable stiffness: flexible with cable end Power circuit: connector 1 4…50 mm² – cable stiffness: solid without cable end Power circuit: connector 2 4…25 mm² – cable stiffness: solid without cable end |
| Tightening torque | Control circuit: 1.2 N.m – on screw clamp terminals – with screwdriver flat Ø 6 mm Control circuit: 1.2 N.m – on screw clamp terminals – with screwdriver Philips No 2 Power circuit: 12 N.m – on connector – with screwdriver flat Ø 6 to Ø 8 mm Power circuit: 12 N.m – on connector hexagonal screw head 4 mm Control circuit: 1.2 N.m – on screw clamp terminals – with screwdriver pozidriv No 2 |
| Auxiliary contact composition | 1 NO + 1 NC |
| Auxiliary contacts type | type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1 type mirror contact 1 NC conforming to IEC 60947-4-1 |
| Signalling circuit frequency | 25…400 Hz |
| Minimum switching voltage | 17 V for signalling circuit |
| Minimum switching current | 5 mA for signalling circuit |
| Insulation resistance | > 10 MOhm for signalling circuit |
| Non-overlap time | 1.5 ms on de-energisation between NC and NO contact 1.5 ms on energisation between NC and NO contact |
| Mounting support | Rail Plate |
| Environment | |
| Standards | EN 60947-4-1 EN 60947-5-1 IEC 60947-4-1 IEC 60947-5-1 CSA C22.2 No 14 UL 60947-4-1 IEC 60335-2-40:Annex JJ UL 60335-2-40:Annex JJ IEC 60335-1:Clause 30.2 |
| Product certifications | CCC UL CB Scheme CSA CE UKCA Marine EAC |
| IP degree of protection | IP20 front face conforming to IEC 60529 |
| Protective treatment | TH conforming to IEC 60068-2-30 |
| Climatic withstand | conforming to IACS E10 exposure to damp heat |
| Permissible ambient air temperature around the device | -40…60 °C 60…70 °C with derating |
| Operating altitude | 0…3000 m |
| Fire resistance | 850 °C conforming to IEC 60695-2-1 |
| Flame retardance | V1 conforming to UL 94 |
| Mechanical robustness | Vibrations contactor open (2 Gn, 5…300 Hz) Shocks contactor open (8 Gn for 11 ms) Vibrations contactor closed (3 Gn, 5…300 Hz) Shocks contactor closed (10 Gn for 11 ms) |
| Height | 127 mm |
| Width | 85 mm |
| Depth | 130 mm |
| Product weight | 1.61 kg |
| Packing Units | |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 13.200 cm |
| Package 1 Width | 13.200 cm |
| Package 1 Length | 9.500 cm |
| Package 1 Weight | 1.551 kg |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 5 |
| Package 2 Height | 15.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 8.057 kg |
| Contractual warranty | |
| Warranty (in months) | 18 |
⚡ Key Features
- 95 A current rating — confirmed from product specifications; size wiring and terminals to match or exceed this value.
- 240V AC coil or control supply voltage — directly compatible with standard panel control circuits.
- Manufactured to IS/IEC 60947, IS 8828 (MCBs), IS 13947, IEC 61439 (DBs) — complies with Indian BIS and IEC international safety standards.
- BIS certified, CE marked, RoHS compliant — meets Indian regulatory requirements for use in government, commercial, and industrial electrical installations.
- Genuine authorised Schneider Electric product — sourced directly from the official distribution network with full manufacturer traceability and warranty.
- GST invoice provided for India orders — valid for corporate procurement, government project orders, and public tender supply via myelectric.in.
- Worldwide export available — UAE, Singapore, UK, USA, Sri Lanka & more. Contact +91 94814 00316 for bulk pricing and international shipping.
🔗 Compatible Products & Accessories
The following genuine accessories and compatible devices are designed to work with this product. Contact myelectric.in for pricing and availability:
❓ Frequently Asked Questions
Q: What is the significance of the 95 A rating on the LC1D95U7?
A: The 95 A rating is the device’s maximum continuous current carrying capacity under specified conditions (typically 40°C ambient). For circuit design, use 80% of this value as the design current to allow for derating due to grouping, temperature, and future load growth.
Q: The LC1D95U7 has a coil voltage of 240V AC — what control supply is needed?
A: This Schneider Electric device requires a 240V AC control supply connected to the coil terminals (A1 and A2). For AC coils, ensure the control circuit voltage is stable — voltage drops below 85% of rated coil voltage can cause chatter and coil overheating. Always fit a surge suppressor across the coil when switching with a PLC or solid-state relay.