A9N3P50CIN | Acti9 xC60 3P C 50A MCB IS/IEC 60947-2 – Schneider Electric
₹5,251.00 Original price was: ₹5,251.00.₹1,837.85Current price is: ₹1,837.85. Excl. GST
Dispatch By : 2 Weeks
Dispatch By : 2 Weeks
Order protection
Buy with complete confidence.
We back each order with genuine supply, on-time dispatch and GST or commercial invoicing as required.
Additional Addons/Accessories
A9N26960 | Voltage release MN 220-240Vac dc – Schneider Electric
A9N26904 | Acti9 A9A iOF bottom wiring 0.1-6A aux – Schneider Electric
A9N26907 | Acti9 A9N SD bottom wiring 0.1-6A aux – Schneider Electric
A9N26923 | Acti 9 – auxiliary contact OFS 1 O/C for RCCB – Schneider Electric
A9N26946 | MX Shunt Trip MX plus 1 OF 220-415Vac dc – Schneider Electric
A9N26948 | MX Shunt Trip MX plus 1 OF 24Vac dc – Schneider Electric
A9N26909 | Acti9 A9N OF/SD+OF top/bt wir 0.1-6A aux – Schneider Electric
The Schneider Electric A9N3P50CIN is a miniature circuit breaker (mcb) from the Acti9 range, engineered for reliable circuit protection and isolation in demanding Indian and international installations. Key ratings include 50 A, 415 V AC 50/60 Hz, 3P. Buy the A9N3P50CIN | Acti9 xC60 3P C 50A MCB IS/IEC 60947-2 online at myelectric.in with GST invoice, genuine-product assurance, and fast delivery across India — bulk and worldwide export enquiries welcome.
📋 Technical Specifications
| Product | |
| Brand | Schneider Electric |
| Part Number / SKU | A9N3P50CIN |
| Category | Miniature Circuit Breaker (MCB) |
| Main | |
| Device application | Distribution |
| Range of product | Acti9 |
| Range | Acti9 |
| Product name | XC60 |
| Product or component type | Miniature circuit-breaker |
| Device short name | xC60 |
| Poles description | 3P |
| Number of protected poles | 3 |
| [In] rated current | 50 A |
| Network type | AC DC |
| Trip unit technology | Thermal-magnetic |
| Curve code | C |
| Utilisation category | Category A conforming to IS/IEC 60947-2 |
| Suitability for isolation | Yes conforming to IS/IEC 60947-2 |
| Complementary | |
| Network frequency | 50/60 Hz |
| [Ue] rated operational voltage | 415 V AC 50/60 Hz 100…125 V DC |
| Magnetic tripping limit | 8 x In +/- 20 % |
| Breaking capacity | 10 kA Inc at 415 V AC 50/60 Hz conforming to IS/IEC 60947-2 15 kA Icu at 100…125 V DC conforming to IS/IEC 60947-2 |
| [Ics] rated service breaking capacity | 7.5 kA conforming to IS/IEC 60947-2 – 415 V AC 50/60 Hz 15 kA conforming to IS/IEC 60947-2 – 100…125 V DC |
| Limitation class | 3 conforming to IS/IEC 60947-2 |
| [Ui] rated insulation voltage | 500 V AC 50/60 Hz conforming to IS/IEC 60947-2 |
| [Uimp] rated impulse withstand voltage | 4 kV conforming to IS/IEC 60947-2 |
| Contact position indicator | Yes |
| Control type | Toggle |
| Local signalling | ON/OFF indication |
| Mounting mode | Clip-on |
| Mounting support | 35 mm DIN rail |
| Comb busbar and distribution block compatibility | Top: YES |
| 9 mm pitches | 6 |
| Height | 85 mm |
| Width | 54 mm |
| Depth | 77.5 mm |
| Product weight | 0.31 kg |
| Colour | White |
| Mechanical durability | 20000 cycles |
| Electrical durability | 10000 cycles |
| Connections – terminals | Biconnect (bottom) Tunnel type terminals (bottom) 25 mm² flexible Tunnel type terminals (bottom) 35 mm² rigid |
| Wire stripping length | 13 mm for top or bottom connection |
| Tightening torque | 3.5 N.m |
| Earth-leakage protection | Separate block |
| Product compatibility | C60 accessories C60 auxiliary |
| Overvoltage category | IV |
| Environment | |
| Standards | IS/IEC 60947-2 |
| IP degree of protection | IP20 |
| Pollution degree | 3 |
| Tropicalisation | 2 conforming to IEC 60068-1 |
| Relative humidity | 95 % at 55 °C |
| Ambient air temperature for operation | -30…70 °C |
| Ambient air temperature for storage | -40…85 °C |
| Packing Units | |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 8.1 cm |
| Package 1 Width | 5.35 cm |
| Package 1 Length | 7.4 cm |
| Package 1 Weight | 390 g |
| Unit Type of Package 2 | BB1 |
| Number of Units in Package 2 | 4 |
| Package 2 Height | 8 cm |
| Package 2 Width | 9 cm |
| Package 2 Length | 23.8 cm |
| Package 2 Weight | 1.622 kg |
| Unit Type of Package 3 | CAR |
| Number of Units in Package 3 | 48 |
| Package 3 Height | 27 cm |
| Package 3 Width | 30 cm |
| Package 3 Length | 35 cm |
| Package 3 Weight | 20.064 kg |
| Contractual warranty | |
| Warranty (in months) | 18 |
⚡ Key Features
- 50 A rated current — provides overload and short-circuit protection for the connected circuit.
- 3 Poles — protects a three-phase circuit without neutral; fits standard 35mm DIN rail in distribution boards.
- Thermal-magnetic trip mechanism — bimetal element trips on sustained overload, instantaneous magnetic trip on short-circuit; two independent protection functions in one compact module.
- Visi-Trip indicator — handle snaps to a clearly visible mid-position on trip, allowing instant fault identification without opening the panel door.
- Compatible with Acti9 comb busbar (1P, 2P, 3P, 3P+N) — parallel wiring of multiple MCBs without individual cables, cutting panel wiring time significantly.
- Manufactured to IS 8828 / IEC 60898-1 (residential) and IEC 60947-2 (industrial) — complies with the applicable Indian BIS and IEC international standards for this product category.
- BIS certified, CE marked, RoHS compliant — meets Indian regulatory requirements for use in government, commercial, and industrial electrical installations.
- Genuine authorised Schneider Electric product — sourced directly from the official distribution network with full manufacturer traceability and warranty.
- GST invoice provided for India orders — valid for corporate procurement, government project orders, and public tender supply via myelectric.in.
- Worldwide export available — UAE, Singapore, UK, USA, Sri Lanka & more. Contact +91 94814 00316 for bulk pricing and international shipping.
❓ Frequently Asked Questions
Q: What load can the A9N3P50CIN protect at its rated 50 A?
A: The A9N3P50CIN is rated to carry and protect circuits up to 50 A continuously. For motor loads, ensure the full-load current (FLC) of the motor does not exceed this rating. For resistive loads (heaters, lighting), the 50 A rating is used directly. Derate by 20% for ambient temperatures above 40°C.
Q: Is the A9N3P50CIN suitable for both single-phase and three-phase systems?
A: The A9N3P50CIN with 3 Poles can protect three-phase circuits. Each pole simultaneously interrupts one phase — ensuring all phases are de-energised on a fault.
Q: Can the A9N3P50CIN be DIN rail mounted in any standard distribution board?
A: Yes. This Schneider Electric MCB uses the standard 35mm EN 60715 DIN rail and 17.5mm module width, making it compatible with all major brand distribution boards and enclosures. Terminal capacity accommodates both rigid and flexible conductors up to the rated cross-section.
Q: What happens when the A9N3P50CIN trips — how do I identify and reset it?
A: When the A9N3P50CIN trips on fault, the handle moves to a midway position (between ON and OFF), distinctly visible from a distance. To reset: (1) identify and rectify the fault, (2) push the handle fully to OFF, (3) then switch back to ON. Never force-reset without investigating the fault cause.
Q: Which Schneider Electric accessories are compatible with the A9N3P50CIN?
A: The Schneider Electric Acti9 series supports snap-on accessories including auxiliary contacts (OF), alarm contacts (SD), shunt trip coils (MX), undervoltage releases (MN), and comb busbars. Accessories are series-specific — always verify compatibility using the Schneider Electric product catalogue before ordering. myelectric.in can advise on the correct accessory part numbers for the A9N3P50CIN.