DU400N MCCB 320A 3P 415V AC 50kA Thermal Magnetic 50 60 Hz L T CM98402OOQO cm98402ooro mccb du400n 400a 3p tm 9in front 1 1
DU400N MCCB 320A 3P 415V AC 50kA Thermal Magnetic 50/60 Hz | L&T - CM98402OOQO Original price was: ₹30,900.00.Current price is: ₹19,158.00. Excl. GST
Back to products
DU400N MCCB 320A 4P 415V AC 50kA Thermal Magnetic 50 60 Hz L T CM98404OOQO cm98404ooro mccb du400n 400a 4p tm 9in front
DU400N MCCB 320A 4P 415V AC 50kA Thermal Magnetic 50/60 Hz | L&T - CM98404OOQO Original price was: ₹38,000.00.Current price is: ₹23,560.00. Excl. GST

DU400N MCCB 400A 3P 415V AC 50kA Thermal Magnetic 50/60 Hz | L&T – CM98402OORO

SKU: CM98402OORO

Original price was: ₹30,900.00.Current price is: ₹19,158.00. Excl. GST

13 People watching this product now!

Order protection

Buy with complete confidence.

We back each order with genuine supply, on-time dispatch and GST or commercial invoicing as required.

Buyer protection on every order
Global DeliveryShipped pan-India and to export markets.
On-Time DeliveryPacked and dispatched on schedule.
100% OriginalFrom brand-authorised channels only.
GST InvoiceCompliant, ITC-ready tax invoice.
Secure PaymentEncrypted, trusted payment gateways.
Also included Dedicated account manager Technical support Bulk & business pricing 3-day replacement

The CM98402OORO CM98402OORO is a mccb, engineered for reliable circuit protection and isolation in demanding Indian and international installations. Key ratings include 400 A, 415V AC, 3 Poles. Buy the DU400N MCCB 400A 3P 415V AC 50kA Thermal Magnetic 50/60 Hz | L&T online at myelectric.in with GST invoice, genuine-product assurance, and fast delivery across India — bulk and worldwide export enquiries welcome.

📋 Technical Specifications

ParameterValue
BrandCM98402OORO
Part Number / SKUCM98402OORO
CategoryMCCB
Current Rating400 A
Voltage Rating415V AC
Poles3 Poles
Breaking Capacity50 kA
Frequency60 Hz
Rated Operational Voltage (Ue)415V AC (50/60 Hz)
MountingFixed, front connected
Rated Frequency50/60 Hz
StandardIEC 60947-2 / IS 13947-2
CertificationsBIS certified where applicable

⚡ Key Features

  • 50 kA breaking capacity at 415V AC — safely clears bolted three-phase faults in high-power substations and MV/LV transformer secondaries.
  • Thermal-magnetic trip unit — factory-calibrated overload and short-circuit protection; suitable for standard feeder circuits without electronic adjustment.
  • 3 Poles — three-phase feeder protection; neutral not switched (TN-C / IT systems).
  • Manufactured to IEC 60947-2 / IS 13947-2 — complies with the applicable Indian BIS and IEC international standards for this product category.
  • BIS certified where applicable — meets Indian regulatory requirements for use in government, commercial, and industrial electrical installations.
  • Genuine authorised CM98402OORO product — sourced directly from the official distribution network with full manufacturer traceability and warranty.
  • GST invoice provided for India orders — valid for corporate procurement, government project orders, and public tender supply via myelectric.in.
  • Worldwide export available — UAE, Singapore, UK, USA, Sri Lanka & more. Contact +91 94814 00316 for bulk pricing and international shipping.

❓ Frequently Asked Questions

Q: What load can the CM98402OORO protect at its rated 400 A?

A: The CM98402OORO is rated to carry and protect circuits up to 400 A continuously. For motor loads, ensure the full-load current (FLC) of the motor does not exceed this rating. For resistive loads (heaters, lighting), the 400 A rating is used directly. Derate by 20% for ambient temperatures above 40°C.

Q: What does the 50 kA breaking capacity on the CM98402OORO mean in practice?

A: Breaking capacity (50 kA) is the maximum prospective short-circuit current the CM98402OORO can safely interrupt without damage. Before installing, verify that the prospective fault level at the installation point does not exceed 50 kA — this is checked using a fault level calculation or from the upstream transformer impedance data. Installing a breaker with insufficient breaking capacity is a serious safety violation.

Q: Can the CM98402OORO be motorised for remote switching and automation?

A: Yes. CM98402OORO MCCBs in this series support rotary handle adaptation and motorised operating mechanisms as accessories, enabling remote ON/OFF switching via PLC, SCADA, or BMS. Motorised MCCBs are used for automatic load management and remote trip in automated distribution systems.

Q: What trip unit type does the CM98402OORO use — thermal-magnetic or electronic?

A: The CM98402OORO uses a thermal-magnetic TMD trip unit — thermal bimetal for overload protection and electromagnetic mechanism for short-circuit. Compact, reliable, and maintenance-free for standard applications.

Q: Is the CM98402OORO suitable for use as a motor branch circuit protector (Type E coordination)?

A: MCCBs used for motor branch circuit protection must be coordinated with the downstream overload relay for Type 2 coordination (no damage to contactor or relay on short-circuit). Verify the CM98402OORO coordination table for the specific contactor-overload-MCCB combination to confirm Type 1 or Type 2 coordination is achieved.

Customer Reviews