GV1L3 | GV2ME-GV2P CURRENT LIMITING – Schneider Electric
₹11,615.00 Original price was: ₹11,615.00.₹5,226.75Current price is: ₹5,226.75. Excl. GST
Dispatch By : 5 Weeks
Dispatch By : 5 Weeks
Order protection
Buy with complete confidence.
We back each order with genuine supply, on-time dispatch and GST or commercial invoicing as required.
Additional Addons/Accessories
GV2ME10 | Motor circuit breaker, TeSys GV2, 3P, 4-6.3 A, thermal magnetic, screw clamp terminals – Schneider Electric
GV2P16 | Motor circuit breaker, TeSys GV2, 3P, 9-14 A, thermal magnetic, screw clamp terminals – Schneider Electric
GV2ME08 | Motor circuit breaker, TeSys GV2, 3P, 2.5-4 A, thermal magnetic, screw clamp terminals – Schneider Electric
GV2ME07 | Motor circuit breaker, TeSys GV2, 3P, 1.6-2.5 A, thermal magnetic, screw clamp terminals – Schneider Electric
GV2ME20 | Motor circuit breaker, TeSys GV2, 3P, 13-18 A, thermal magnetic, screw clamp terminals – Schneider Electric
Looking for the GV1L3 | GV2ME-GV2P CURRENT LIMITING? This genuine Schneider Electric motor protection circuit breaker (mpcb) from the TeSys range is built for reliable circuit protection and isolation, combining proven reliability with full compliance to applicable IEC/IS standards. Key ratings include 32 A, 690 V AC 50/60 Hz. Order part number GV1L3 from myelectric.in — a trusted Schneider Electric supplier offering competitive pricing, GST billing, and shipping across India and overseas.
📋 Technical Specifications
| Product | |
| Brand | Schneider Electric |
| Part Number / SKU | GV1L3 |
| Category | Motor Protection Circuit Breaker (MPCB) |
| Main | |
| Range | TeSys |
| Range of product | TeSys GV2 TeSys Deca |
| Accessory / separate part category | Protection accessory |
| Product or component type | Current limiting module |
| Range compatibility | TeSys GV2 TeSys Deca |
| Product compatibility | GV2RT GV2ME GV2P GV2L |
| Function of module | Increasing the breaking capacity of a circuit breaker |
| Mounting location | On top of the circuit breaker |
| [Ie] rated operational current | 32 A |
| [Ith] conventional free air thermal current | 63 A conforming to IEC 60947-1 |
| Activation threshold | 1500 A |
| Breaking capacity | <= 100 kA depending on protective device |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz |
| [Ui] rated insulation voltage | 690 V AC 50/60 Hz conforming to IEC 60947-1 |
| Complementary | |
| Connections – terminals | Screw clamp terminals 1 x 1.5…25 mm² rigid Screw clamp terminals 2 x 1.5…10 mm² rigid Screw clamp terminals 1 x 1.5…25 mm² flexible without cable end Screw clamp terminals 2 x 1.5…10 mm² flexible without cable end Screw clamp terminals 1 x 1.5…16 mm² flexible with cable end Screw clamp terminals 2 x 1.5…4 mm² flexible with cable end |
| tightening torque | 2.2 N.m |
| Product weight | 0.13 kg |
| Packing Units | |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 8.5 cm |
| Package 1 Width | 5.0 cm |
| Package 1 Length | 8.0 cm |
| Package 1 Weight | 122.0 g |
| Unit Type of Package 2 | S01 |
| Number of Units in Package 2 | 24 |
| Package 2 Height | 15.0 cm |
| Package 2 Width | 15.0 cm |
| Package 2 Length | 40.0 cm |
| Package 2 Weight | 3.104 kg |
| Contractual warranty | |
| Warranty (in months) | 18 |
⚡ Key Features
- Combined thermal and magnetic protection in one device — single MPCB replaces a separate motor-rated MCB plus thermal overload relay, saving DIN rail space and inter-device wiring.
- Phase-loss and phase-unbalance detection — trips within seconds of a phase failure, protecting the motor from the severe overheating that single-phasing causes within minutes.
- Manual reset only — operator must acknowledge and reset the MPCB after a trip, preventing automatic restart that could damage the motor or driven machinery.
- Manufactured to IEC 60947-4-1 and IEC 60947-2 — complies with the applicable Indian BIS and IEC international standards for this product category.
- BIS certified, CE marked, RoHS compliant — meets Indian regulatory requirements for use in government, commercial, and industrial electrical installations.
- Genuine authorised Schneider Electric product — sourced directly from the official distribution network with full manufacturer traceability and warranty.
- GST invoice provided for India orders — valid for corporate procurement, government project orders, and public tender supply via myelectric.in.
- Worldwide export available — UAE, Singapore, UK, USA, Sri Lanka & more. Contact +91 94814 00316 for bulk pricing and international shipping.
🔗 Compatible Products & Accessories
The following genuine accessories and compatible devices are designed to work with this product. Contact myelectric.in for pricing and availability:
❓ Frequently Asked Questions
Q: Can the GV1L3 replace a contactor + overload relay combination in a motor circuit?
A: The GV1L3 provides motor short-circuit protection and overload protection in one device — but it cannot make/break motor current under normal operational switching (that is the contactor’s role). For motor starters requiring on/off switching, the GV1L3 is used as the upstream protection device with a contactor for switching. Some MPCB series include a direct handle for manual starting of small motors without a separate contactor.
Q: What is the trip class of the GV1L3 and what motor starting time does it allow?
A: MPCBs are typically rated Class 10 (trips in ≤10 seconds at 7.2× setting current), suitable for normal motors with DOL starting times up to 10 seconds. Heavy-duty motors (large fans, centrifuges, compressors) with longer starting times may need Class 20 or Class 30 protection — check the starting time against the motor’s speed-torque curve and select accordingly.
Q: Which Schneider Electric accessories are compatible with the GV1L3?
A: The Schneider Electric GV1L3 series supports snap-on accessories including auxiliary contacts (OF), alarm contacts (SD), shunt trip coils (MX), undervoltage releases (MN), and comb busbars. Accessories are series-specific — always verify compatibility using the Schneider Electric product catalogue before ordering. myelectric.in can advise on the correct accessory part numbers for the GV1L3.
Q: What is the difference between a Motor Protection Circuit Breaker (MPCB) and a standard MCB — and why use the GV1L3?
A: A standard MCB protects against overload and short-circuit only. A Motor Protection Circuit Breaker (MPCB) adds adjustable thermal overload matched to motor FLC, Class 10/20 trip curves for motor starting inrush, and phase-loss sensitivity — making it the correct device for motor branch circuits where a standard MCB would either nuisance-trip on motor starting or fail to protect adequately against slow overloads. Choose the GV1L3 when the application specifically requires motor protection circuit breaker (mpcb) characteristics.