A9N4P32D miniature circuit breaker xC60 4 poles 32 A D curve Schneider Electric pb110814 1500x1500
A9N4P04C | miniature circuit breaker - xC60 - 4 poles - 4 A - C curve - Schneider Electric Original price was: $76.04.Current price is: $26.61. Excl. GST
Back to products
A9N4P32D miniature circuit breaker xC60 4 poles 32 A D curve Schneider Electric pb110814 1500x1500
A9N4P06D | miniature circuit breaker - xC60 - 4 poles - 6 A - D curve - Schneider Electric Original price was: $64.09.Current price is: $22.43. Excl. GST

A9N4P06C | miniature circuit breaker – xC60 – 4 poles – 6 A – C curve – Schneider Electric

SKU: A9N4P06C

Original price was: $61.80.Current price is: $17.30. Excl. GST

Out of stock

Out of stock

13 People watching this product now!

Order protection

Buy with complete confidence.

We back each order with genuine supply, on-time dispatch and GST or commercial invoicing as required.

Buyer protection on every order
Global DeliveryShipped pan-India and to export markets.
On-Time DeliveryPacked and dispatched on schedule.
100% OriginalFrom brand-authorised channels only.
GST InvoiceCompliant, ITC-ready tax invoice.
Secure PaymentEncrypted, trusted payment gateways.
Also included Dedicated account manager Technical support Bulk & business pricing 3-day replacement

The Schneider Electric A9N4P06C is a miniature circuit breaker (mcb) from the Acti9 range, engineered for reliable circuit protection and isolation in demanding Indian and international installations. Key ratings include 6 A, 220…240 V AC 50/60 Hz, 4P. Buy the A9N4P06C | miniature circuit breaker – xC60 – 4 poles – 6 A – C curve online at myelectric.in with GST invoice, genuine-product assurance, and fast delivery across India — bulk and worldwide export enquiries welcome.

📋 Technical Specifications

Product
BrandSchneider Electric
Part Number / SKUA9N4P06C
CategoryMiniature Circuit Breaker (MCB)
Main
Device applicationDistribution
Range of productActi9
RangeActi9
Product nameXC60
Product or component typeMiniature circuit-breaker
Device short namexC60
Poles description4P
Number of protected poles4
[In] rated current6 A
Network typeAC
Trip unit technologyThermal-magnetic
Curve codeC
Complementary
Network frequency50/60 Hz
[Ue] rated operational voltage220…240 V AC 50/60 Hz
380…415 V AC 50/60 Hz
Magnetic tripping limit5…10 x In
Breaking capacity10000 A Icn at 240 V AC 50/60 Hz conforming to IS/IEC 60898-1
10000 A Icn at 415 V AC 50/60 Hz conforming to IS/IEC 60898-1
Limitation class3 conforming to IS/IEC 60898-1
Contact position indicatorYes
Control typeToggle
Local signallingON/OFF indication
Mounting modeClip-on
Mounting support35 mm DIN rail
Comb busbar and distribution block compatibilityTop: YES
9 mm pitches8
Height85 mm
Width72 mm
Depth77.5 mm
Product weight0.415 kg
ColourWhite
Mechanical durability20000 cycles
Electrical durability20000 cycles
Connections – terminalsTunnel type terminals (bottom) 16 mm² flexible
Tunnel type terminals (bottom) 25 mm² rigid
Biconnect (bottom)
Wire stripping length13 mm for top or bottom connection
Tightening torque2 N.m
Earth-leakage protectionSeparate block
Product compatibilityC60 accessories
C60 auxiliary
Overvoltage categoryIV
Environment
StandardsIS/IEC 60898-1
IP degree of protectionIP20
Pollution degree3
Tropicalisation2 conforming to IEC 60068-1
Relative humidity95 % at 55 °C
Ambient air temperature for operation-30…70 °C
Ambient air temperature for storage-40…85 °C
Packing Units
Unit Type of Package 1PCE
Number of Units in Package 11
Package 1 Height8.1 cm
Package 1 Width7.15 cm
Package 1 Length7.4 cm
Package 1 Weight470 g
Unit Type of Package 2BB1
Number of Units in Package 23
Package 2 Height8 cm
Package 2 Width9 cm
Package 2 Length23.8 cm
Package 2 Weight1.472 kg
Unit Type of Package 3CAR
Number of Units in Package 336
Package 3 Height27 cm
Package 3 Width30 cm
Package 3 Length35 cm
Package 3 Weight18.264 kg
Contractual warranty
Warranty (in months)18

⚡ Key Features

  • 6 A rated current — provides overload and short-circuit protection for the connected circuit.
  • Curve C tripping characteristic — optimised for general-purpose and inductive loads (motors, mixed circuits) — trips magnetically at 5–10× rated current.
  • 4 Poles — protects a three-phase four-wire circuit with switched neutral; fits standard 35mm DIN rail in distribution boards.
  • Thermal-magnetic trip mechanism — bimetal element trips on sustained overload, instantaneous magnetic trip on short-circuit; two independent protection functions in one compact module.
  • Manufactured to IS 8828 / IEC 60898-1 (residential) and IEC 60947-2 (industrial) — complies with the applicable Indian BIS and IEC international standards for this product category.
  • BIS certified, CE marked, RoHS compliant — meets Indian regulatory requirements for use in government, commercial, and industrial electrical installations.
  • Genuine authorised Schneider Electric product — sourced directly from the official distribution network with full manufacturer traceability and warranty.
  • GST invoice provided for India orders — valid for corporate procurement, government project orders, and public tender supply via myelectric.in.
  • Worldwide export available — UAE, Singapore, UK, USA, Sri Lanka & more. Contact +91 94814 00316 for bulk pricing and international shipping.

❓ Frequently Asked Questions

Q: What load can the A9N4P06C protect at its rated 6 A?

A: The A9N4P06C is rated to carry and protect circuits up to 6 A continuously. For motor loads, ensure the full-load current (FLC) of the motor does not exceed this rating. For resistive loads (heaters, lighting), the 6 A rating is used directly. Derate by 20% for ambient temperatures above 40°C.

Q: Why is Curve C specified for the A9N4P06C and what loads is it optimised for?

A: Curve C on the A9N4P06C trips magnetically at 5–10× rated current, making it ideal for general-purpose circuits including fluorescent lamps, small motors, and mixed loads. Using the wrong curve can cause nuisance tripping (too sensitive) or inadequate protection (not sensitive enough). Always match the curve to the load’s inrush characteristics.

Q: Is the A9N4P06C suitable for both single-phase and three-phase systems?

A: The A9N4P06C with 4 Poles can protect three-phase circuits. Each pole simultaneously interrupts one phase — ensuring all phases are de-energised on a fault.

Q: Can the A9N4P06C be DIN rail mounted in any standard distribution board?

A: Yes. This Schneider Electric MCB uses the standard 35mm EN 60715 DIN rail and 17.5mm module width, making it compatible with all major brand distribution boards and enclosures. Terminal capacity accommodates both rigid and flexible conductors up to the rated cross-section.

Q: What happens when the A9N4P06C trips — how do I identify and reset it?

A: When the A9N4P06C trips on fault, the handle moves to a midway position (between ON and OFF), distinctly visible from a distance. To reset: (1) identify and rectify the fault, (2) push the handle fully to OFF, (3) then switch back to ON. Never force-reset without investigating the fault cause.

Customer Reviews