VCF2GE TeSys Vario enclosed, emergency switch disconnector, 32A, IP65 Schneider Electric oda9348 se 1500x1500
VCF2GE | TeSys Vario enclosed, emergency switch disconnector, 32A, IP65 - Schneider Electric Original price was: ₹11,560.00.Current price is: ₹7,167.20. Excl. GST
Back to products
VCF3GE TeSys Vario enclosed, emergency switch disconnector, 50A, IP65 Schneider Electric odapg114001 se 1500x1500
VCF3GE | TeSys Vario enclosed, emergency switch disconnector, 50A, IP65 - Schneider Electric Original price was: ₹17,870.00.Current price is: ₹11,079.40. Excl. GST

VCF3 | TeSys Vario – emergency stop switch disconnector – 63 A – on door – Schneider Electric

SKU: VCF3

Original price was: ₹14,775.00.Current price is: ₹8,421.75. Excl. GST

In stock

In stock

10 People watching this product now!

Order protection

Buy with complete confidence.

We back each order with genuine supply, on-time dispatch and GST or commercial invoicing as required.

Buyer protection on every order
Global DeliveryShipped pan-India and to export markets.
On-Time DeliveryPacked and dispatched on schedule.
100% OriginalFrom brand-authorised channels only.
GST InvoiceCompliant, ITC-ready tax invoice.
Secure PaymentEncrypted, trusted payment gateways.
Also included Dedicated account manager Technical support Bulk & business pricing 3-day replacement

The Schneider Electric VCF3 is a switch disconnector from the TeSys range, engineered for reliable circuit protection and isolation in demanding Indian and international installations. Key ratings include 41.5 A AC-23 Ue: 400 V, 690 V AC 50/60 Hz, 3P. Buy the VCF3 | TeSys Vario – emergency stop switch disconnector – 63 A – on door online at myelectric.in with GST invoice, genuine-product assurance, and fast delivery across India — bulk and worldwide export enquiries welcome.

📋 Technical Specifications

Product
BrandSchneider Electric
Part Number / SKUVCF3
CategorySwitch Disconnector
Main
RangeTeSys
Product NameTeSys VARIO
Device Short NameVCF
Product TypeEmergency stop switch disconnector
Complementary
Device CompositionSwitch
Handle
Mounting SupportHandle: door
Switch: door
Mounting MethodBy 4 screws for handle
Performance LevelHigh performance
Number of Poles3P
Contact Type and Composition3 NO
[Ue] IEC Rated Operational Voltage690 V AC 50/60 Hz
IEC Rated Operational Power in W11 kW at 230…240 V (AC-3)
22 kW at 500 V (AC-3)
22 kW at 690 V (AC-23A)
30 kW at 500 V (AC-23A)
18.5 kW at 400…415 V (AC-3)
18.5 kW at 690 V (AC-3)
15 kW at 230…240 V (AC-23A)
22 kW at 400…415 V (AC-23A)
[Ie] Rated Operational Current41.5 A AC-23 Ue: 400 V
[Ith] Conventional Free Air Thermal Current63 A
[Ithe] Conventional Enclosed Thermal Current50 A
Making Capacity ( I Rms)630 A at 400 V AC-21A
630 A at 400 V AC-22A
630 A at 400 V AC-23A
Breaking Capacity500 A at 400 V (AC-21A)
500 A at 400 V (AC-22A)
500 A at 400 V (AC-23A)
Rated Conditional Short Circuit Current10 kA at 400 V – associated fuse 63 A aM
10 kA at 400 V – associated fuse 63 A gG
[Icm] Rated Short Circuit Making Capacity2.1 kA at 400 V at Ipeak
[Icw] Rated Short Time Withstand Current756 A at 400 V duration: 1 s
[Uimp] Rated Impulse Withstand Voltage8 kV
Suitability for IsolationYes
Network TypeDC
AC
Intermittent Duty Class30
Control TypeRotary handle
Rotary Handle Mounting StyleDirect
Handle ColorRed
Handle Front Plate ColorYellow
Rotary Handle Padlocking1 to 3 padlocks 4…8 mm
Marking0 – 1
Mechanical Durability30000 cycles
Electrical Durability30000 cycles AC-21
30000 cycles DC-1…5
IEC Terminal ConnectionPower circuit: screw clamp terminals25 mm² – solid
Power circuit: screw clamp terminals16 mm² – flexible – with cable end
Tightening TorquePower circuit: 4 N.m – on screw clamp terminals
Base Dimension60 x 60 mm
Height83 mm
Width60 mm
Product Weight0.56 kg
Environment
StandardsIEC 60947-3
Product CertificationsGL
CCC
CSA
UL
UKCA
Degree of ProtectionIP20 conforming to IEC 60529
IP65
Protective TreatmentTC
Mechanical RobustnessVibrations 10…150 Hz (1 gn) conforming to IEC 60068-2-6
Shocks 11 ms (30 Gn) conforming to IEC 60068-2-27
Ambient Air Temperature for Operation-20…50 °C
Fire Resistance960 °C conforming to IEC 60695-2-1
Compatibility CodeMain switch disconnector
Packing Units
Unit Type of Package 1PCE
Number of Units in Package 11
Package 1 Height7.800 cm
Package 1 Width8.500 cm
Package 1 Length11.800 cm
Package 1 Weight349.000 g
Unit Type of Package 2S02
Number of Units in Package 212
Package 2 Height15.000 cm
Package 2 Width30.000 cm
Package 2 Length40.000 cm
Package 2 Weight4.500 kg
Unit Type of Package 3P06
Number of Units in Package 3192
Package 3 Height75.000 cm
Package 3 Width60.000 cm
Package 3 Length80.000 cm
Package 3 Weight81.060 kg
Contractual warranty
Warranty (in months)18

⚡ Key Features

  • 63 A current rating — confirmed from product specifications; size wiring and terminals to match or exceed this value.
  • Manufactured to IS/IEC 60947, IS 8828 (MCBs), IS 13947, IEC 61439 (DBs) — complies with Indian BIS and IEC international safety standards.
  • BIS certified, CE marked, RoHS compliant — meets Indian regulatory requirements for use in government, commercial, and industrial electrical installations.
  • Genuine authorised Schneider Electric product — sourced directly from the official distribution network with full manufacturer traceability and warranty.
  • GST invoice provided for India orders — valid for corporate procurement, government project orders, and public tender supply via myelectric.in.
  • Worldwide export available — UAE, Singapore, UK, USA, Sri Lanka & more. Contact +91 94814 00316 for bulk pricing and international shipping.

🔗 Compatible Products & Accessories

The following genuine accessories and compatible devices are designed to work with this product. Contact myelectric.in for pricing and availability:

VZ9VZ7VZ12VZ20VZ15VZ3

❓ Frequently Asked Questions

Q: What is the significance of the 63 A rating on the VCF3?

A: The 63 A rating is the device’s maximum continuous current carrying capacity under specified conditions (typically 40°C ambient). For circuit design, use 80% of this value as the design current to allow for derating due to grouping, temperature, and future load growth.

Q: Can the VCF3 make and break load current, or is it for isolation only?

A: This is a switch-disconnector (not a pure isolator), meaning it is rated to make and break load currents up to its rated current under AC-22A or AC-23A utilisation categories. Pure isolators must only be operated on de-energised circuits. The Schneider Electric switch-disconnector can therefore be used for operational switching, not just maintenance isolation.

Q: How many padlocks can be applied to the VCF3 for LOTO safety?

A: The Schneider Electric switch disconnector supports up to 3 simultaneous padlocks on the OFF-position locking facility. This allows multiple contractors or maintenance teams to each apply their own padlock, ensuring the circuit cannot be re-energised until all teams have removed their lock — a critical requirement for multi-contractor LOTO procedures.