Sourced through authorised channels, the Schneider Electric VCF2GE switch disconnector from the TeSys range delivers dependable performance for reliable circuit protection and isolation. Key ratings include 29 A, 690 V AC, 3P. myelectric.in stocks the VCF2GE | TeSys Vario enclosed, emergency switch disconnector, 32A, IP65 for contractors, panel builders, and project buyers — buy online with GST invoice, or request a bulk quote for domestic supply and export to UAE, Singapore, UK, USA, Sri Lanka and more.
📋 Technical Specifications
| Product | |
| Brand | Schneider Electric |
| Part Number / SKU | VCF2GE |
| Category | Switch Disconnector |
| Main | |
| Range | TeSys |
| Product name | TeSys VARIO |
| Device short name | VCF |
| Product or component type | Enclosed emergency stop switch disconnector |
| Performance level | High performance |
| Poles description | 3P |
| Control type | Rotary handle |
| Handle colour | Red |
| Handle front plate colour | Yellow |
| Rotary handle padlocking | 1 to 3 padlocks 4…8 mm |
| Complementary | |
| Marking | 0 – 1 |
| [Ue] rated operational voltage | 690 V AC |
| [Uimp] rated impulse withstand voltage | 8 kV |
| [Ithe] conventional enclosed thermal current | 32 A |
| [Ie] rated operational current | 29 A (AC-23A) at 400 V |
| Rated operational power in W | 15 kW at 400 V (AC-23) 11 kW at 400 V (AC-3) |
| Intermittent duty class | 30 |
| Making capacity ( I rms) | 400 A at 400 V AC-21A 400 A at 400 V AC-22A 400 A at 400 V AC-23A |
| [Icm] rated short-circuit making capacity | 1 kA at 400 V at Ipeak |
| [Icw] rated short-time withstand Rms current | 480 A at 400 V duration: 1 s |
| Rated conditional short-circuit current | 10 kA at 400 V – associated fuse 50 A aM 10 kA at 400 V – associated fuse 50 A gG |
| Breaking capacity | 320 A at 400 V (AC-21A) 320 A at 400 V (AC-22A) 320 A at 400 V (AC-23A) |
| Mechanical durability | 100000 cycles |
| Electrical durability | 100000 cycles AC-21 30000 cycles DC-1…5 |
| Environmental characteristic | Standard environment |
| Suitability for isolation | Yes |
| Connections – terminals | Screw clamp terminals10 mm² – solid Screw clamp terminals6 mm² – flexible – with cable end |
| Tightening torque | 2.1 N.m – on screw clamp terminals |
| Fire resistance | 960 °C conforming to IEC 60595-2-1 |
| handle front plate dimension | 60 x 60 mm |
| Height | 146 mm |
| Width | 90 mm |
| Depth | 131 mm |
| Product weight | 0.5 kg |
| Environment | |
| Standards | IEC 60204 IEC 60947-4-1 |
| Protective treatment | TC |
| IP degree of protection | IP65 conforming to IEC 60529 |
| Mechanical robustness | Vibrations 10…150 Hz (1 gn) conforming to IEC 60068-2-6 Shocks 11 ms (30 Gn) conforming to IEC 60068-2-27 |
| Ambient air temperature for operation | -20…50 °C |
| Packing Units | |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 14.500 cm |
| Package 1 Width | 11.300 cm |
| Package 1 Length | 15.800 cm |
| Package 1 Weight | 473.000 g |
| Unit Type of Package 2 | S03 |
| Number of Units in Package 2 | 7 |
| Package 2 Height | 30.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 3.764 kg |
| Unit Type of Package 3 | P06 |
| Number of Units in Package 3 | 56 |
| Package 3 Height | 75.000 cm |
| Package 3 Width | 60.000 cm |
| Package 3 Length | 80.000 cm |
| Package 3 Weight | 40.244 kg |
| Contractual warranty | |
| Warranty (in months) | 18 |
⚡ Key Features
- 32 A current rating — confirmed from product specifications; size wiring and terminals to match or exceed this value.
- IP65 enclosure rating — confirmed ingress protection against dust and moisture for the installation environment.
- Manufactured to IS/IEC 60947, IS 8828 (MCBs), IS 13947, IEC 61439 (DBs) — complies with Indian BIS and IEC international safety standards.
- BIS certified, CE marked, RoHS compliant — meets Indian regulatory requirements for use in government, commercial, and industrial electrical installations.
- Genuine authorised Schneider Electric product — sourced directly from the official distribution network with full manufacturer traceability and warranty.
- GST invoice provided for India orders — valid for corporate procurement, government project orders, and public tender supply via myelectric.in.
- Worldwide export available — UAE, Singapore, UK, USA, Sri Lanka & more. Contact +91 94814 00316 for bulk pricing and international shipping.
🔗 Compatible Products & Accessories
The following genuine accessories and compatible devices are designed to work with this product. Contact myelectric.in for pricing and availability:
❓ Frequently Asked Questions
Q: What is the significance of the 32 A rating on the VCF2GE?
A: The 32 A rating is the device’s maximum continuous current carrying capacity under specified conditions (typically 40°C ambient). For circuit design, use 80% of this value as the design current to allow for derating due to grouping, temperature, and future load growth.
Q: What environments is the IP65 rating on the VCF2GE suitable for?
A: IP65 means the enclosure is dust-tight (complete protection) (first digit: 6) and protected against water protection (second digit: 5). This makes the VCF2GE suitable for indoor-outdoor transitional areas, splash-prone locations. Always verify IP integrity after installation — damaged seals or unused cable entries reduce actual protection.
Q: How many padlocks can be applied to the VCF2GE for LOTO safety?
A: The Schneider Electric switch disconnector supports up to 3 simultaneous padlocks on the OFF-position locking facility. This allows multiple contractors or maintenance teams to each apply their own padlock, ensuring the circuit cannot be re-energised until all teams have removed their lock — a critical requirement for multi-contractor LOTO procedures.
Q: Can the VCF2GE make and break load current, or is it for isolation only?
A: This is a switch-disconnector (not a pure isolator), meaning it is rated to make and break load currents up to its rated current under AC-22A or AC-23A utilisation categories. Pure isolators must only be operated on de-energised circuits. The Schneider Electric switch-disconnector can therefore be used for operational switching, not just maintenance isolation.